Operating instructions

26 Installation Drawings
Figure 8 Outline Drawing: 100 – 250 Amp STS2 with a Key Lockout Switch Option
STATICSWITCH2/OUTLINE/PS211101
11/6/02
PS211101
GRAVITY
SIDE VIEW
TOP VIEW
BOTTOM ENTRY AREA
POWER CABLE
BOTTOM ENTRY AREA
CONTROL CABLE
BOTTOM VIEW
FRONT VIEW
EXHAUST
TOP ENTRY AREA
TOP ENTRY AREA
POWER CABLE
CONTROL CABLE
FRONT
FRONT
MAX. DOOR SWING 180°
CENTER
GRAVITY
CENTER
2. 18" (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.
9. OPEN DOOR TO REPLACE AIR FILTER, DISPOSABLE TYPE, SIZE 1X25X25.
STAND. NOTE, IF FLOORSTAND IS USED THE WEIGHT OF THE UNIT MUST
10. THREADED MOUNTING HOLES USED FOR SEISMIC ANCHORING OR FLOOR-
11. EACH MOUNTING LOCATION IS SUPPORTED BY (2) 10 GA. (.135")
GALVANIZED STEEL. THE THREADED 12MM INSERT IS APPROX. 3/4" DEEP.
MOUNTING BOLTS MUST BE THREADED INTO UNIT MOUNTING HOLES FROM
7. KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.
6. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.
4680 BTU/HR (1.37 KW/HR) MAX. FOR 250A SWITCH.
4. HEAT OUTPUT: 2710 BTU/HR (0.80 KW/HR) MAX. FOR 100A SWITCH.
3. INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY.
1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).
BE SUPPORTED UNDER ALL CASTERS.
UNDERNEATH UNIT BASE.
8. COLOR - IBM OFF WHITE.
NOTES:
5. WEIGHT - 780 LBS. (354 KG)
SEE DETAIL A
CENTERS
CASTER
CENTERS
12MM
AIR
CENTERS
CASTER
12MM CENTERS
AIR FILTER
AIR INTAKE AREA
DO NOT BLOCK
OUTLINE DRAWING
100 - 250 AMP WITH KEY LOCKOUT SWITCH OPTION
STATIC TRANSFER SWITCH 2
DETAIL A
WITHOUT SIDE PANEL
FRONT OF UNIT SHOWN
(SEE NOTES 10 & 11)
12MM DIA THREADED
MOUNTING HOLE (4) TYP
LEVELER
DATE
FILE NAME:
COLUMBUS, OHIO 43229
1050 DEARBORN DRIVE,
REV. NO.
DWG. NO.
V CARMONA
REF. DWG.
CHK BY
DRAWN BY
KEY LOCKOUT
SWITCH