Operating instructions

Installation Drawings 25
Figure 7 Outline Drawing: 800 – 1000 Amp STS2
BOTTOM
POWER CABLE
AIR FILTER
DO NOT BLOCK
AIR INTAKE AREA
FRONT VIEW
CABINET
TOP ENTRY AREA
CONTROL CABLE
TOP ENTRY AREA
POWER CABLE
(TYP)
SIDE VIEW
TOP VIEWBOTTOM VIEW
SEE DETAIL A
FRONT
FRONT
AIR EXHAUST
GRAVITY
CENTER
5. WEIGHT - 2500 LBS. (1134 KG)
UNDERNEATH UNIT BASE.
BE SUPPORTED UNDER ALL CASTERS.
8. COLOR - IBM OFF WHITE.
MOUNTING BOLTS MUST BE THREADED INTO UNIT MOUNTING HOLES FROM
GALVANIZED STEEL. THE THREADED 12MM INSERT IS APPROX. 3/4" DEEP.
2. 18" (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.
9. OPEN DOOR TO REPLACE AIR FILTER, DISPOSABLE TYPE, SIZE 1X25X25.
STAND. NOTE, IF FLOORSTAND IS USED THE WEIGHT OF THE UNIT MUST
10. THREADED MOUNTING HOLES USED FOR SEISMIC ANCHORING OR FLOOR-
11. EACH MOUNTING LOCATION IS SUPPORTED BY (2) 10 GA. (.135")
7. KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.
6. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.
3. INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY.
1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).
4. HEAT OUTPUT: 13780 BTU/HR (4.03 KW/HR) MAX. FOR 800A SWITCH.
MAX. DOOR SWING 180° (TYP)
NOTES:
17390 BTU/HR (5.09 KW/HR) MAX. FOR 1000A SWITCH.
CONTROL CABLE
BOTTOM ENTRY AREA
CENTERS
12MM
CASTER
CENTERS
12MM
CENTERS
GRAVITY
CENTER
BREAKER
CASTER
CENTERS
12. 500 CFM PER EXHAUST FAN.
ENTRY AREA
FILE NAME:
REV. NO.
DWG. NO.
OUTLINE DRAWING
800 - 1000 AMP
STATIC TRANSFER SWITCH 2
DRAWN BY
REF. DWG.
CHK BY
V CARMONA
STATICSWITCH2/OUTLINE/PS211800
PS211800
DATE
10/23/02
COLUMBUS, OHIO 43229
1050 DEARBORN DRIVE,
DETAIL A
WITHOUT SIDE PANEL
FRONT OF UNIT SHOWN
(SEE NOTES 10 & 11)
MOUNTING HOLE (8) TYP
12MM DIA THREADED
LEVELER