Operating instructions

24 Installation Drawings
Figure 6 Outline Drawing: 400 – 600 Amp STS2
FRONT VIEW SIDE VIEW
CONTROL CABLE
TOP ENTRY AREA
CABLE
TOP ENTRY AREA
EXHAUST
CONTROL CABLE
BOTTOM ENTRY AREA
POWER CABLE
BOTTOM ENTRY
BOTTOM VIEW TOP VIEW
GRAVITY
FRONT
FRONT
MAX. DOOR SWING 180° (TYP)
CENTER
GRAVITY
CENTER
UNDERNEATH UNIT BASE.
MOUNTING BOLTS MUST BE THREADED INTO UNIT MOUNTING HOLES FROM
GALVANIZED STEEL. THE THREADED 12MM INSERT IS APPROX. 3/4" DEEP.
2. 18" (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.
9. OPEN DOOR TO REPLACE AIR FILTER, DISPOSABLE TYPE, SIZE 1X25X25.
STAND. NOTE, IF FLOORSTAND IS USED THE WEIGHT OF THE UNIT MUST
10. THREADED MOUNTING HOLES USED FOR SEISMIC ANCHORING OR FLOOR-
11. EACH MOUNTING LOCATION IS SUPPORTED BY (2) 10 GA. (.135")
7. KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.
6. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.
4. HEAT OUTPUT: 6970 BTU/HR (2.04 KW/HR) MAX. FOR 400A SWITCH.
3. INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY.
1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).
BE SUPPORTED UNDER ALL CASTERS.
8. COLOR - IBM OFF WHITE.
5. WEIGHT - 1200 LBS. (544 KG)
NOTES:
10520 BTU/HR (3.08 KW/HR) MAX. FOR 600A SWITCH.
SEE DETAIL A
AREA
CENTERS
12MM
CASTER
CENTERS
AIR
12MM CENTERS
CASTER
CENTERS
DO NOT BLOCK
AIR INTAKE AREA
AIR FILTER
POWER
FILE NAME:
REV. NO.
DWG. NO.
OUTLINE DRAWING
400 - 600 AMP
STATIC TRANSFER SWITCH 2
DRAWN BY
REF. DWG.
CHK BY
V CARMONA
STATICSWITCH2/OUTLINE/PS211400
PS211400
DATE
10/23/02
COLUMBUS, OHIO 43229
1050 DEARBORN DRIVE,
DETAIL A
WITHOUT SIDE PANEL
FRONT OF UNIT SHOWN
MOUNTING HOLE (4) TYP
(SEE NOTES 10 & 11)
12MM DIA THREADED
LEVELER