Operating instructions

96 STS2 Touch Screen Display
Figure 49 History Log
To use the History Log:
1. Select LOGS from the menu bar to open the Logs menu.
2. Select either HISTORY LOG 1 or HISTORY LOG 2 from the menu.
3. Select the appropriate buttons to replay the log:
Select PREV to go to the previous frame in the sequence.
Select NEXT to go to the next frame in the sequence.
Move the green cursor to the location from which you would like to play the sequence of
events.
Select REPLAY to play the frames automatically from the point of the cursor.
Select STOP to halt the replay.
Select RESET to return to the first frame in the log.
4. Select EXIT to close the History Log. The data remains in the log.
Use CLEAR HLOGS to remove the data from both history logs.
13.6.3 Source Transfers
The Source Transfer choice (SOURCE XFERS) allows you to manually select a preferred source.
To switch the primary source, refer to the instructions in Manual Transfer / Preferred Source
Selection on page 59.
13.6.4 Startup Procedure
You can access instructions for starting the STS2 from the menu bar.
From the menu bar, select STARTUP PROC.
These instructions are also provided on 10.1 - Normal System Turn-On on page 58 for Color
Graphical display units and 14.2.1 - Normal System Turn-On on page 103 for LED Display
units.
13.6.5 Bypass Procedure
You can access instructions for bypassing the static transfer switch from the menu bar.
From the menu bar, select BYP. PROC.
The instructions are provided in the display panel.
Bypass procedures are also discussed in 10.4 - Maintenance Bypass on page 61 for Color Graphi-
cal display units and 14.2.3 - Maintenance Bypass on page 104 for LED Display units.
NOTE
Event and History Logs are protected by security. The password or a