Brochures and Data Sheets
Emerson Network Power.com
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
™
.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
+63 2 730 9572 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2009 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
SL-23318 (R09/09) Printed in USA
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2009 Emerson Electric Co.
Liebert PSI XR Specifications
Model Number PS1000RT3-120 PS1500RT3-120 PS2200RT3-120 PS3000RT3-120
Network Solutions Package Number
PS1000RT3-120W PS1500RT3-120W PS2200RT3-120W PS3000RT3-120W
Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W 3000VA/2700W
Dimensions, W x D x H, in (mm)
Unit 17.3 x 16.2 x 3.5
(440 x 412 x 88)
17.3 x 16.2x 3.5
(440 x 412 x 88)
17.3 x 25.9 x 3.5
(440 x 657x 88)
17.3 x 25.9 x 3.5
(440 x 657x 88)
Shipping 22 x 24.1 x 9 (560 x 612 x 228) 22 x 24.1 x 9 (560 x 612 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228)
Weight, lb (kg)
Unit 43 (20) 47 (21) 76 (35) 84 (38)
Shipping 51 (23) 54 (25) 84 (38) 93 (42)
Input AC Parameters
Surge Protection 570J
Voltage Range Without Battery
Operation
83 to 159 VAC (configurable)
Frequency Range 45~65Hz, (0.5Hz)
Input Power Cord, 10ft (3m)
attached
NEMA 5-15P plug NEMA 5-15P plug NEMA 5-20P plug NEMA L5-30P plug
Output Receptacles (8) NEMA 5-15R (8) NEMA 5-15R (6) NEMA 5-15R (2) NEMA 5-20R
T-Slot, accepts 15A Plug
(6) NEMA 5-15R (2) NEMA 5-20R
T-Slot, accepts 15A Plug
Voltage (Normal Mode) 110/120/127 VAC (configurable)
Voltage (Battery Mode) 110/120/127 VAC; 5% before low-battery warning
Transfer Time 4-6 ms typical
Battery Waveform Sinewave
Battery Parameters
Typ e Valve-regulated, non-spillable, lead acid
Recharge Time 5 hours to 90% of rated capacity, after full discharge into resistive load
Battery Backup Time
Full Load 4 min 3 min 3 min 3 min
Half Load 12 min 9 min 11 min 9 min
Environmental
Operating Temperature, ˚F (˚C) 32 to 104 (0 to 40)
Storage Temperature, ˚F (˚C) 5 to 104 (-15 to 40)
Relative Humidity 0% to 90%, non-condensing
Operating Altitude Up to 10,000 ft (3000m) at 95˚F (35˚C) without derating
Audible Noise <40 dBA, internal fan(s) Off; <45 dBA, internal fan(s) On
Agency
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class A
Network Surge UL 497 B
Transportation ISTA Procedure 1A Certification
Rail Kit (included)
Rail Kit RAILKITPS3G-AEC
NEC limits the input current rating of the 2200VA model to 80% of the input plug’s rating. If 1920 or more is required, contact a certified electrician to change the input plug to
30A plug. Emerson Network Power assumes no liability for damage caused by miswiring or misapplication of the input plug.