Precision Cooling For Business-Critical Continuity™ Liebert Dual Unit Control for InteleCool® and InteleCool2® User Manual
TABLE OF CONTENTS 1.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1.1 Connecting the Dual Unit Controller to an Electronic Thermostat . . . . . . . . . . . . . . . . . . . . 1 1.1.1 1.1.2 Connecting the Dual Unit Controller to an InteleCool2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Connecting the Dual Unit Controller to the InteleCool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation 1.0 INSTALLATION The optional Dual Unit Control is designed to control two InteleCool or two InteleCool2® units in a lead/lag fashion. The control contains an electronic timer for switching the operating sequence of two units at intervals of one, two, four or eight days. It also contains a two-stage heat/two-stage cool electronic thermostat with individual heat and cool setpoints. Light emitting diodes (LEDs) indicate Lead Unit 1 or 2 and power to Unit 1 or Unit 2.
Installation 1.1.2 Connecting the Dual Unit Controller to the InteleCool 1. Install and level the Dual Unit Control.Leveling is not critical because the electronic thermostat does not contain mercury-filled limit switches. 2. Wire the InteleCool units to the Dual Unit Control using industry-standard thermostat cable. Each InteleCool will need at least 4 conductor, 20 gauge, Class 2 copper wire for distances up to 50 feet (15.2m). Use 18 gauge, Class 2 copper wire for distances between 50 and 75 feet (15.
Control Startup 2.0 CONTROL STARTUP 2.1 Start the Dual Unit Control 1. Turn the thermostat Off. 2. Turn on power to both InteleCool2 units. 3. Turn on circuit breakers in each InteleCool2. Both green “POWER ON” LED’s and 1 of the green “LEAD UNIT” LED’s of the Dual Unit Control will be lit if the unit has been properly connected. 4. Turn the thermostat switch to the “Auto” setting. One or both of the InteleCool2 units should start if the thermostat is in a call for heating or cooling. 2.
Control Startup Figure 1 Dual Unit Control Board 1 P5 2 P5 to LED Panel Reverse P4 4 1 2 Normal R 3 Y Unit 2 1/2 DRAWING IS NOT TO SCALE W Slow Fast P1 P3 3 4 1 2 R 3 P1 to Thermostat 4 Y Unit 1 1/2 5 6 7 W TB1 8/4Day 4/2Day 2/1Day Lead1 Lead2 P2 ! Table 2 WARNING S e r v i c e InteleCool and InteleCool2 units contain potentially lethal voltage. Shut off power before performing any service work.
Disposal of Dual Unit Control 3.0 DISPOSAL OF DUAL UNIT CONTROL Some thermostats used on this control may contain mercury in a sealed tube. Do not place the control in the trash at the end of its useful life. If this control is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash.
Ensuring The High Availability 0f Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity.