Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 70
Table 20 Liebert XDP
™
- Status and Coil
Controller Liebert iCOM
®
v4
Data Label
Status Coil Number of Bits Notes
Pumps
Pump 1 Loss of Flow 10001 — 1 Active on Alarm
Pump 2 Loss of Flow 10002 — 1 Active on Alarm
Pump Short Cycle 10020 — 1 Active on Alarm
System Events
Fan Issue 10003 — 1 Active on Alarm
System Condensation Detected 10004 — 1 Active on Alarm
Customer Input 1 10005 — 1 Active on Alarm
Shutdown - Loss Of Power 10019 — 1 Active on Alarm
Water Under Floor 10021 — 1 Active on Alarm
Smoke Detected 10022 — 1 Active on Alarm
Service Required 10023 — 1 Active on Alarm
Unit Communication Lost 10262 — 1 Active on Alarm
RAM Battery Issue 10263 — 1 Active on Alarm
Master Unit Communication Lost 10264 — 1 Active on Alarm
Remote Shutdown 10265 — 1 Active on Alarm
Unit Code Missing 10266 — 1 Active on Alarm
Chilled Water
Supply Chilled Water Over Temp 10006 — 1 Active on Alarm
Supply Chilled Water Temp Sensor Issue 10007 — 1 Active on Alarm
Chilled Water Control Valve Position 10018 — 1 Active on Alarm
Refrigerant
Supply Refrigerant Over Temp 10008 — 1 Active on Alarm
Supply Refrigerant Under Temp 10009 — 1 Active on Alarm
Supply Refrigerant Temp Sensor Issue 10010 — 1 Active on Alarm
External Air
Ext Air Sensor A Over Temperature 10011 — 1 Active on Alarm
Ext Air Sensor A Under Temperature 10012 — 1 Active on Alarm
Ext Air Sensor A Issue 10013 — 1 Active on Alarm
Ext Air Sensor B Over Temperature 10014 — 1 Active on Alarm
Ext Air Sensor B Under Temperature 10015 — 1 Active on Alarm
Ext Air Sensor B Issue 10016 — 1 Active on Alarm
Ext Dew Point Over Temperature 10017 — 1 Active on Alarm
Pump Hours 1
Pump Hours Exceeded 10030 — 1 Active on Alarm
Pump Hours 2
Pump Hours Exceeded 10036 — 1 Active on Alarm
XD System 1 —
Ext System Condensation Detected 10042 — 1 Active on Alarm
Ext Fan Issue 10043 — 1 Active on Alarm
Sensor Issue 10044 — 1 Active on Alarm
Ext Remote Shutdown 10045 — 1 Active on Alarm
Hot Aisle Temp Out of Range 10046 — 1 Active on Alarm
Cold Aisle Temp Out of Range 10047 — 1 Active on Alarm