Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
47 Liebert
®
IntelliSlot
®
Modbus/BACnet
System Operating State Current operating state of the system.
System Static Pressure
Static pressure measurement among a group of interconnected
units in a single system.
System Status The operating status for the system
Temperature Control Sensor Issue
The air sensor selected for cooling control is disconnected or the
signal is out of range.
Today's High Air Temperature Time [Today's High Air Temperature] was measured at this time.
Today's High Air Temperature The highest external air temperature measured since midnight.
Today's High Humidity Time [Today's High Humidity] was measured at this time
Today's High Humidity The highest external humidity measured since midnight.
Today's Low Air Temperature Time [Today's Low Air Temperature] was measured at this time.
Today's Low Air Temperature The lowest external air temperature measured since midnight.
Today's Low Humidity Time [Today's Low Humidity] was measured at this time
Today's Low Humidity The lowest external humidity measured since midnight.
Unit Code Missing Unit code has not been entered and saved.
Unit Communication Lost Master has lost communication with one or more networked units.
Unit Cooling Load
The total amount of heat energy currently being removed by the
unit.
Unit Off Unit was turned off.
Unit On Unit was turned on.
Unit Partial Shutdown
An event has occurred requiring some system components to be
shutdown and disabled.
Unit Shutdown
An event has occurred requiring the unit to be shutdown and
disabled to prevent damage to the system.
Unit Standby Unit was placed in standby mode.
Unit Static Pressure Static pressure measurement for a single unit.
Unspecified General Event
One or more unspecified events active. See local unit display for
further details.
Water Leakage Detector Sensor Issue
The water leakage detector sensor is disconnected or the signal is
out of range.
Water Under Floor - Event Control
Enable/disable the activation of the [Water Under Floor] event. If
set to “disabled,” the event will not be annunciated. This implies
that the event will not be placed in any active event list or in any
event history list.
Water Under Floor - Event Type The event type for the [Water Under Floor] event.
Water Under Floor Water under the floor is detected.
Table 10 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Glossary (continued)
Controller Liebert iCOM
®
v4
Data Label Data Description