Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 40
Ext Humidifier Lockout - Event Control
Enable/disable the activation of the [Ext Humidifier Lockout] event.
If set to “disabled,” the event will not be annunciated. This implies
that the event will not be placed in any active event list or in any
event history list.
Ext Humidifier Lockout - Event Type The event type for the [Ext Humidifier Lockout] event.
Ext Humidifier Lockout
The humidifier is shut down and disabled by an external input
signal.
Ext Loss of Air Blower - Event Control
Enable/disable the activation of the [Ext Loss of Air Blower] event.
If set to “disabled,” the event will not be annunciated. This implies
that the event will not be placed in any active event list or in any
event history list.
Ext Loss of Air Blower - Event Type The event type for the [Ext Loss of Air Blower] event.
Ext Loss of Air Blower
Loss of air blower is detected, as indicated by an external input
signal.
Ext Loss of Flow - Event Control
Enable/disable the activation of the [Ext Loss of Flow] event. If set
to “disabled,” the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event
history list.
Ext Loss of Flow - Event Type The event type for the [Ext Loss of Flow] event.
Ext Loss of Flow Loss of flow is detected, as indicated by an external input signal.
Ext Over Temperature - Event Control
Enable/disable the activation of the [Ext Over Temperature] event.
If set to “disabled,” the event will not be annunciated. This implies
that the event will not be placed in any active event list or in any
event history list.
Ext Over Temperature - Event Type The event type for the [Ext Over Temperature] event.
Ext Over Temperature
A temperature has exceeded its threshold, as indicated by an
external input signal.
Ext Power Source A Failure
Unit main power source A failure, as indicated by an external input
signal.
Ext Power Source B Failure
Unit main power source B failure, as indicated by an external input
signal.
Ext Reheat Lockout - Event Control
Enable/disable the activation of the [Ext Reheat Lockout] event. If
set to “disabled,” the event will not be annunciated. This implies
that the event will not be placed in any active event list or in any
event history list.
Ext Reheat Lockout - Event Type The event type for the [Ext Reheat Lockout] event.
Ext Reheat Lockout The reheater is shut down and disabled by an external input signal.
Ext Standby Glycol Pump On - Event Control
Enable/disable the activation of the [Ext Standby Glycol Pump On]
event. If set to “disabled,” the event will not be annunciated. This
implies that the event will not be placed in any active event list or in
any event history list.
Ext Standby Glycol Pump On - Event Type The event type for the [Ext Standby Glycol Pump On] event.
Ext Standby Glycol Pump On
The standby glycol pump is on, as indicated by an external input
signal.
Ext Standby Unit On - Event Control
Enable/disable the activation of the [Ext Standby Unit On] event. If
set to “disabled,” the event will not be annunciated. This implies
that the event will not be placed in any active event list or in any
event history list.
Ext Standby Unit On - Event Type The event type for the [Ext Standby Unit On] event.
Ext Standby Unit On Standby unit is on, as indicated by an external input signal.
Table 10 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Glossary (continued)
Controller Liebert iCOM
®
v4
Data Label Data Description