Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 30
Fluid Input Temperature 2 30901 — 1 10 deg C 5
Fluid Input Temperature 1 30902 — 1 10 deg F 5
Fluid Input Temperature 2 30903 — 1 10 deg F 5
Fluid Output Temperature 1 30904 — 1 10 deg C 5
Fluid Output Temperature 2 30905 — 1 10 deg C 5
Fluid Output Temperature 1 30906 — 1 10 deg F 5
Fluid Output Temperature 2 30907 — 1 10 deg F 5
Fluid Flow Rate 1 30908 — 2 10 l/min 5
Fluid Flow Rate 2 30910 — 2 10 l/min 5
Unit Cooling Load 31001 — 2 10 kW 5
Circuit Cooling Load 1 31003 — 2 10 kW 5
Circuit Cooling Load 2 31005 — 2 10 kW 5
Instantaneous Power 1 31010 — 2 — W 5
Instantaneous Power 2 31012 — 2 — W 5
Instantaneous Power 3 31014 — 2 — W 5
Instantaneous Power 4 31016 — 2 — W 5
Instantaneous Power 5 31018 — 2 — W 5
Instantaneous Power 6 31020 — 2 — W 5
Raw Auxiliary Air Temperature 31050 41050 1 10 deg C 5
Raw Auxiliary Air Temperature 31051 41051 1 10 deg F 5
Actual Auxiliary Air Temperature 31052 — 1 10 deg C 5
Actual Auxiliary Air Temperature 31053 — 1 10 deg F 5
System Input RMS A-B 1 31060 — 1 10 VAC 5
System Input RMS A-B 2 31061 — 1 10 VAC 5
System Input RMS A-B 3 31062 — 1 10 VAC 5
System Input RMS A-B 4 31063 — 1 10 VAC 5
System Input RMS A-B 5 31064 — 1 10 VAC 5
System Input RMS A-B 6 31065 — 1 10 VAC 5
System Input RMS B-C 1 31070 — 1 10 VAC 5
System Input RMS B-C 2 31071 — 1 10 VAC 5
System Input RMS B-C 3 31072 — 1 10 VAC 5
System Input RMS B-C 4 31073 — 1 10 VAC 5
System Input RMS B-C 5 31074 — 1 10 VAC 5
System Input RMS B-C 6 31075 — 1 10 VAC 5
System Input RMS C-A 1 31080 — 1 10 VAC 5
System Input RMS C-A 2 31081 — 1 10 VAC 5
System Input RMS C-A 3 31082 — 1 10 VAC 5
System Input RMS C-A 4 31083 — 1 10 VAC 5
System Input RMS C-A 5 31084 — 1 10 VAC 5
System Input RMS C-A 6 31085 — 1 10 VAC 5
Pump State 1 31100 — 1 —
0 = off
1 = on
8, 9
Table 8 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra