Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
29 Liebert
®
IntelliSlot
®
Modbus/BACnet
System Input RMS C-N 3 30822 1 10 VAC 5
System Input RMS C-N 4 30823 1 10 VAC 5
System Input RMS C-N 5 30824 1 10 VAC 5
System Input RMS C-N 6 30825 1 10 VAC 5
System Input RMS Current Phase A
1
30830 1 10 A AC 5
System Input RMS Current Phase A
2
30831 1 10 A AC 5
System Input RMS Current Phase A
3
30832 1 10 A AC 5
System Input RMS Current Phase A
4
30833 1 10 A AC 5
System Input RMS Current Phase A
5
30834 1 10 A AC 5
System Input RMS Current Phase A
6
30835 1 10 A AC 5
System Input RMS Current Phase B
1
30840 1 10 A AC 5
System Input RMS Current Phase B
2
30841 1 10 A AC 5
System Input RMS Current Phase B
3
30842 1 10 A AC 5
System Input RMS Current Phase B
4
30843 1 10 A AC 5
System Input RMS Current Phase B
5
30844 1 10 A AC 5
System Input RMS Current Phase B
6
30845 1 10 A AC 5
System Input RMS Current Phase C
1
30850 1 10 A AC 5
System Input RMS Current Phase C
2
30851 1 10 A AC 5
System Input RMS Current Phase C
3
30852 1 10 A AC 5
System Input RMS Current Phase C
4
30853 1 10 A AC 5
System Input RMS Current Phase C
5
30854 1 10 A AC 5
System Input RMS Current Phase C
6
30855 1 10 A AC 5
Energy Consumption 1 30870 40870 2 kWH 5
Energy Consumption 2 30872 40872 2 kWH 5
Energy Consumption 3 30874 40874 2 kWH 5
Energy Consumption 4 30876 40876 2 kWH 5
Energy Consumption 5 30878 40878 2 kWH 5
Energy Consumption 6 30880 40880 2 kWH 5
Fluid Input Temperature 1 30900 1 10 deg C 5
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes