Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
29 Liebert
®
IntelliSlot
®
Modbus/BACnet
System Input RMS C-N 3 30822 — 1 10 VAC 5
System Input RMS C-N 4 30823 — 1 10 VAC 5
System Input RMS C-N 5 30824 — 1 10 VAC 5
System Input RMS C-N 6 30825 — 1 10 VAC 5
System Input RMS Current Phase A
1
30830 — 1 10 A AC 5
System Input RMS Current Phase A
2
30831 — 1 10 A AC 5
System Input RMS Current Phase A
3
30832 — 1 10 A AC 5
System Input RMS Current Phase A
4
30833 — 1 10 A AC 5
System Input RMS Current Phase A
5
30834 — 1 10 A AC 5
System Input RMS Current Phase A
6
30835 — 1 10 A AC 5
System Input RMS Current Phase B
1
30840 — 1 10 A AC 5
System Input RMS Current Phase B
2
30841 — 1 10 A AC 5
System Input RMS Current Phase B
3
30842 — 1 10 A AC 5
System Input RMS Current Phase B
4
30843 — 1 10 A AC 5
System Input RMS Current Phase B
5
30844 — 1 10 A AC 5
System Input RMS Current Phase B
6
30845 — 1 10 A AC 5
System Input RMS Current Phase C
1
30850 — 1 10 A AC 5
System Input RMS Current Phase C
2
30851 — 1 10 A AC 5
System Input RMS Current Phase C
3
30852 — 1 10 A AC 5
System Input RMS Current Phase C
4
30853 — 1 10 A AC 5
System Input RMS Current Phase C
5
30854 — 1 10 A AC 5
System Input RMS Current Phase C
6
30855 — 1 10 A AC 5
Energy Consumption 1 30870 40870 2 — kWH 5
Energy Consumption 2 30872 40872 2 — kWH 5
Energy Consumption 3 30874 40874 2 — kWH 5
Energy Consumption 4 30876 40876 2 — kWH 5
Energy Consumption 5 30878 40878 2 — kWH 5
Energy Consumption 6 30880 40880 2 — kWH 5
Fluid Input Temperature 1 30900 — 1 10 deg C 5
Table 8 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes