Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 28
Digital Scroll Compressor Loading 2 30669 — 1 — %
3, 4, 5, 6, 7, 8,
9
Static Pressure Set Point 30672 40672 1 10 Pa 3, 4, 5, 9
Unit Static Pressure 30673 — 1 10 Pa 3, 4, 5, 9
System Static Pressure 30674 — 1 10 Pa 3, 4, 5, 9
Condenser Low Noise Mode State 30675 — 1 —
0 = Inactive
1 = Active (Interval)
2 = Active (Full Day)
3, 4, 5, 6, 7, 8,
9
Condenser Low Noise Mode
Schedule Control
30676 40676 1 —
0 = disabled
1 = enabled
3, 4, 5, 6, 7, 8,
9
Condenser Low Noise Mode Max
Fan Speed
30677 40677 1 — %
3, 4, 5, 6, 7, 8,
9
Condenser Normal Mode Max Fan
Speed
30678 40678 1 — %
3, 4, 5, 6, 7, 8,
9
Condenser Low Noise Mode -
Interval Days
30679 40679 1 —
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
3, 4, 5, 6, 7, 8,
9
Condenser Low Noise Mode - Full
Days
30680 40680 1 —
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
3, 4, 5, 6, 7, 8,
9
Condenser Low Noise Mode Start
Time
30681 40681 2 — Seconds since Midnight
3, 4, 5, 6, 7, 8,
9
Condenser Low Noise Mode Stop
Time
30683 40683 2 — Seconds since Midnight
3, 4, 5, 6, 7, 8,
9
Pump Hours 1 30685 40685 2 — hr 7, 8, 9
Pump Hours 2 30687 40687 2 — hr 7, 8, 9
System Input RMS A-N 1 30800 — 1 10 VAC 5
System Input RMS A-N 2 30801 — 1 10 VAC 5
System Input RMS A-N 3 30802 — 1 10 VAC 5
System Input RMS A-N 4 30803 — 1 10 VAC 5
System Input RMS A-N 5 30804 — 1 10 VAC 5
System Input RMS A-N 6 30805 — 1 10 VAC 5
System Input RMS B-N 1 30810 — 1 10 VAC 5
System Input RMS B-N 2 30811 — 1 10 VAC 5
System Input RMS B-N 3 30812 — 1 10 VAC 5
System Input RMS B-N 4 30813 — 1 10 VAC 5
System Input RMS B-N 5 30814 — 1 10 VAC 5
System Input RMS B-N 6 30815 — 1 10 VAC 5
System Input RMS C-N 1 30820 — 1 10 VAC 5
System Input RMS C-N 2 30821 — 1 10 VAC 5
Table 8 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes