Technical Specifications
BACnet Communications - UPS Systems
333 Liebert
®
IntelliSlot
®
Modbus/BACnet
System Output RMS Current Phs B Analog_Value 57 4205_1 RD Units: A AC
System Output RMS Current Phs C Analog_Value 58 4206_1 RD Units: A AC
System Output Frequency Analog_Value 59 4207_1 RD Units: Hz
System Output Voltage RMS A-B Analog_Value 60 4201_1 RD Units: VAC
System Output Voltage RMS B-C Analog_Value 61 4202_1 RD Units: VAC
System Output Voltage RMS C-A Analog_Value 62 4203_1 RD Units: VAC
System Output Power Factor Phs A Analog_Value 63 4210_1 RD —
System Output Power Factor Phs B Analog_Value 64 4211_1 RD —
System Output Power Factor Phs C Analog_Value 65 4212_1 RD —
System Output Pct Power Phase A Analog_Value 66 4223_1 RD Units: %
System Output Pct Power Phase B Analog_Value 67 4224_1 RD Units: %
System Output Pct Power Phase C Analog_Value 68 4225_1 RD Units: %
MMS Output Apparent Power Analog_Value 69 4812_1 RD Units: kVA
MMS Output Power Analog_Value 70 4811_1 RD Units: kW
System Output Apparent Power Analog_Value 71 4209_1 RD Units: kVA
System Output Power Analog_Value 72 4208_1 RD Units: kW
Output Current Crest Factor Phs A Analog_Value 73 5159_1 RD —
Output Current Crest Factor Phs B Analog_Value 74 5160_1 RD —
Output Current Crest Factor Phs C Analog_Value 75 5161_1 RD —
System Configuration
System Date and Time Analog_Value 86 4293_1 RW —
Table 104 Liebert APM
™
, Liebert NXC
™
, Liebert NXR
™
- Multistate Data
Data Label
Object
Type Instance
Object
Name Access Notes
Battery
UPS battery1 status MultiState_Value 1 4871_1 RD
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
System Status
Inverter On/Off State MultiState_Value 12 4746_1 RD
1 = off
2 = on
Maintenance Bypass Breaker (MBB) MultiState_Value 13 4772_1 RD
1 = Open
2 = Close
3 = Not Installed
UPS Output Source MultiState_Value 14 4872_1 RD
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reduced
System Status MultiState_Value 15 4123_1 RD
1 = Normal Operation
2 = StartUp
3 = Normal with Warning
4 = Normal with Alarm
5 = Abnormal Operation
ECO Mode Operation State MultiState_Value 16 5454_1 RD
1 = disabled
2 = enabled
Table 103 Liebert APM
™
, Liebert NXC
™
, Liebert NXR
™
- Analog Data (continued)
Data Label
Object Type Instance Object Name Access Notes