Technical Specifications

BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 324
Compressor 2B Short Cycle - Event
Control
Enable/disable the activation of the [Compressor 2B Short Cycle] event. If set
to “disabled,” the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Compressor 2B Short Cycle - Event Type The event type for the [Compressor 2B Short Cycle] event.
Compressor 2B Short Cycle
Compressor 2B short cycle. A short cycle is defined as turning on and off a
number of times over a set time period.
Compressor 2B State Compressor 2B operational state.
Cooling Capacity
Cooling capacity in use, expressed as a percentage of the maximum rated
capacity.
Cooling Capacity Cooling capacity in use, expressed in kilowatts.
Customer Input 1 - Event Control
Enable/disable the activation of the [Customer Input 1] event. If set to
“disabled,” the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Customer Input 1 - Event Type The event type for the [Customer Input 1] event.
Customer Input 1 Customer input 1.
Dew Point Temperature Dew point temperature, using the highest reading from all sensors.
Ext Air Over Temp Threshold
Threshold value used in the ([Ext Air Sensor A Over Temperature], [Ext Air
Sensor B Over Temperature]...) events.
Ext Air Sensor A Dew Point Temp Dew point temperature as measured by external air sensor A.
Ext Air Sensor A Humidity Relative humidity as measured by external air sensor A.
Ext Air Sensor A Issue - Event Control
Enable/disable the activation of the [Ext Air Sensor A Issue] event. If set to
“disabled,” the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Ext Air Sensor A Issue - Event Type The event type for the [Ext Air Sensor A Issue] event.
Ext Air Sensor A Issue The external air sensor A is disconnected or the signal is out of range.
Ext Air Sensor A Over Temp - Event
Control
Enable/disable the activation of the [Ext Air Sensor A Over Temperature]
event. If set to “disabled,” the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Ext Air Sensor A Over Temp - Event Type The event type for the [Ext Air Sensor A Over Temperature] event.
Ext Air Sensor A Over Temperature [Ext Air Sensor A Temperature] has exceeded [Ext Air Over Temp Threshold].
Ext Air Sensor A Temperature Air temperature as measured by external air sensor A.
Ext Air Sensor A Under Temp - Event
Control
Enable/disable the activation of the [Ext Air Sensor A Under Temperature]
event. If set to “disabled,” the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Ext Air Sensor A Under Temp - Event Type The event type for the [Ext Air Sensor A Under Temperature] event.
Ext Air Sensor A Under Temperature
[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp
Threshold].
Ext Air Sensor B Dew Point Temp Dew point temperature as measured by external air sensor B.
Ext Air Sensor B Humidity Relative humidity as measured by external air sensor B.
Ext Air Sensor B Issue - Event Control
Enable/disable the activation of the [Ext Air Sensor B Issue] event. If set to
“disabled,” the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Ext Air Sensor B Issue - Event Type The event type for the [Ext Air Sensor B Issue] event.
Ext Air Sensor B Issue The external air sensor B is disconnected or the signal is out of range.
Ext Air Sensor B Over Temp - Event
Control
Enable/disable the activation of the [Ext Air Sensor B Over Temperature]
event. If set to “disabled,” the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Ext Air Sensor B Over Temp - Event Type The event type for the [Ext Air Sensor B Over Temperature] event.
Ext Air Sensor B Over Temperature [Ext Air Sensor B Temperature] has exceeded [Ext Air Over Temp Threshold].
Table 99 Liebert XDP
, Liebert XDC
- Glossary (continued)
Data Label Data Description