Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
27 Liebert
®
IntelliSlot
®
Modbus/BACnet
Remote Sensor Temperature 5 30555 — 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 5 30775 — 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 6 30556 — 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 6 30776 — 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 7 30557 — 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 7 30777 — 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 8 30558 — 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 8 30778 — 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 9 30559 — 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 9 30779 — 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 10 30560 — 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 10 30780 — 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Air Economizer Availability 30561 — 1 —
0 = Not Available
1 = Available
2, 3, 4, 5, 6, 7,
8, 9
Air Economizer Control Source 30562 40562 1 —
0 = disabled
1 = internal
2 = external
2, 3, 4, 5, 6, 7,
8, 9
Chilled Water Valve Hours 30563 40563 1 — hr
2, 3, 4, 5, 6, 7,
8, 9
Cooling Capacity 30564 — 1 — %
2, 3, 4, 5, 6, 7,
8, 9
Cooling Control Temperature 30565 — 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Cooling Control Temperature 30781 — 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Fan Speed Control Temperature 30566 — 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Fan Speed Control Temperature 30782 — 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Free Cooling Internal Control Mode 30567 40567 1 —
0 = Disabled
1 = Contact
2 = Temperature
3 = Set Point
2, 3, 4, 5, 6, 7,
8, 9
Humidity Control Sensor 30667 40667 1 —
0 = Supply
1 = Remote
2 = Return
3, 4, 5, 6, 7, 8,
9
Digital Scroll Compressor Loading 1 30668 — 1 — %
3, 4, 5, 6, 7, 8,
9
Table 8 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra