Technical Specifications
BACnet Communications - Thermal Management Products
323 Liebert
®
IntelliSlot
®
Modbus/BACnet
Cold Aisle Temp Out of Range
The air temperature in the cold aisle is either above [Cold Aisle Over Temp
Threshold] or below [Cold Aisle Under Temp Threshold].
Cold Aisle Under Temp Threshold Lower threshold value used in the [Cold Aisle Temp Out of Range] event.
Communication Status Communication status of remote device.
Compressor 1A High Head Pressure -
Event Control
Enable/disable the activation of the [Compressor 1A High Head Pressure]
event. If set to “disabled,” the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Compressor 1A High Head Pressure -
Event Type
The event type for the [Compressor 1A High Head Pressure] event.
Compressor 1A High Head Pressure Compressor 1A high head pressure.
Compressor 1A Short Cycle - Event
Control
Enable/disable the activation of the [Compressor 1A Short Cycle] event. If set
to “disabled,” the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Compressor 1A Short Cycle - Event Type The event type for the [Compressor 1A Short Cycle] event.
Compressor 1A Short Cycle
Compressor 1A short cycle. A short cycle is defined as turning on and off a
number of times over a set time period.
Compressor 1A State Compressor 1A operational state.
Compressor 1B High Head Pressure -
Event Control
Enable/disable the activation of the [Compressor 1B High Head Pressure]
event. If set to “disabled,” the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Compressor 1B High Head Pressure -
Event Type
The event type for the [Compressor 1B High Head Pressure] event.
Compressor 1B High Head Pressure Compressor 1B high head pressure.
Compressor 1B Short Cycle - Event
Control
Enable/disable the activation of the [Compressor 1B Short Cycle] event. If set
to “disabled,” the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Compressor 1B Short Cycle - Event Type The event type for the [Compressor 1B Short Cycle] event.
Compressor 1B Short Cycle
Compressor 1B short cycle. A short cycle is defined as turning on and off a
number of times over a set time period.
Compressor 1B State Compressor 1B operational state.
Compressor 2A High Head Pressure -
Event Control
Enable/disable the activation of the [Compressor 2A High Head Pressure]
event. If set to “disabled,” the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Compressor 2A High Head Pressure -
Event Type
The event type for the [Compressor 2A High Head Pressure] event.
Compressor 2A High Head Pressure Compressor 2A high head pressure.
Compressor 2A Short Cycle - Event
Control
Enable/disable the activation of the [Compressor 2A Short Cycle] event. If set
to “disabled,” the event will not be annunciated. This implies that the event will
not be placed in any active event list or in any event history list.
Compressor 2A Short Cycle - Event Type The event type for the [Compressor 2A Short Cycle] event.
Compressor 2A Short Cycle
Compressor 2A short cycle. A short cycle is defined as turning on and off a
number of times over a set time period.
Compressor 2A State Compressor 2A operational state.
Compressor 2B High Head Pressure -
Event Control
Enable/disable the activation of the [Compressor 2B High Head Pressure]
event. If set to “disabled,” the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Compressor 2B High Head Pressure -
Event Type
The event type for the [Compressor 2B High Head Pressure] event.
Compressor 2B High Head Pressure Compressor 2B high head pressure.
Table 99 Liebert XDP
™
, Liebert XDC
™
- Glossary (continued)
Data Label Data Description