Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 26
Actual Humidity Set Point 30502 1 % RH
2, 3, 4, 5, 6, 7,
8, 9
Dew Point Set Point 30503 40503 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Dew Point Set Point 30764 40764 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Supply Air Over/Under Temperature
- Event Control
30504 40504 1
0 = disabled
1 = enabled
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Over Temp
Threshold
30505 40505 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Over Temp
Threshold
30765 40765 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Under Temp
Threshold
30506 40506 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Under Temp
Threshold
30766 40766 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Average
Temperature
30507 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Average
Temperature
30767 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Maximum
Temperature
30508 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Maximum
Temperature
30768 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor System Average
Temperature
30509 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor System Average
Temperature
30769 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor System Maximum
Temperature
30510 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor System Maximum
Temperature
30770 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 1 30551 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 1 30771 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 2 30552 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 2 30772 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 3 30553 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 3 30773 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 4 30554 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Remote Sensor Temperature 4 30774 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes