Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 24
Low Return Humidity - Event Type 30366 40366 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Return Air Over Temp - Event
Control
30367 40367 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Return Air Over Temp - Event Type 30368 40368 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Return Air Under Temp - Event
Control
30369 40369 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Return Air Under Temp - Event Type 30370 40370 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Fan Hours Exceeded - Event
Control
30371 40371 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Fan Hours Exceeded - Event Type 30372 40372 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Fan Issue - Event Control 30373 40373 1 —
0 = disabled
1 = enabled
1
Fan Issue - Event Type 30374 40374 1 —
0 = Message
1 = Warning
2 = Alarm
1
Main Fan Overload - Event Control 30375 40375 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Main Fan Overload - Event Type 30376 40376 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Condenser Issue - Event Control 1 30377 40377 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Condenser Issue - Event Control 2 30378 40378 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Condenser Issue - Event Type 1 30379 40379 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Condenser Issue - Event Type 2 30380 40380 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
System Event Acknowledge/Reset — 40381 1 —
2 = Reset
4 = Acknowledge
1, 2, 3, 4, 5, 6,
7, 8, 9
Air Temperature Control Sensor 30481 40481 1 —
0 = Supply
1 = Remote
2 = Return
2, 3, 4, 5, 6, 7,
8, 9
Supply Air Over Temp Threshold 30482 40482 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Supply Air Over Temp Threshold 30755 40755 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Supply Air Under Temp Threshold 30483 40483 1 10 deg C
2, 3, 4, 5, 6, 7,
8, 9
Supply Air Under Temp Threshold 30756 40756 1 10 deg F
2, 3, 4, 5, 6, 7,
8, 9
Table 8 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes