Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
23 Liebert
®
IntelliSlot
®
Modbus/BACnet
Compressor Short Cycle - Event
Type 2
30346 40346 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Thermal Overload -
Event Control 1
30347 40347 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Thermal Overload -
Event Control 2
30348 40348 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Thermal Overload -
Event Type 1
30349 40349 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Thermal Overload -
Event Type 2
30350 40350 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Dig Scroll Comp Discharge Over
Temp - Event Ctrl 1
30351 40351 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Dig Scroll Comp Discharge Over
Temp - Event Ctrl 2
30352 40352 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Dig Scroll Comp Discharge Over
Temp - Event Type 1
30353 40353 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Dig Scroll Comp Discharge Over
Temp - Event Type 2
30354 40354 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A High Humidity -
Event Control
30355 40355 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A High Humidity -
Event Type
30356 40356 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Low Humidity -
Event Control
30357 40357 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Low Humidity -
Event Type
30358 40358 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Over Temp - Event
Control
30359 40359 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Over Temp - Event
Type
30360 40360 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Under Temp -
Event Control
30361 40361 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Under Temp -
Event Type
30362 40362 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
High Return Humidity - Event
Control
30363 40363 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
High Return Humidity - Event Type 30364 40364 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Low Return Humidity - Event Control 30365 40365 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes