Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 22
Ext Compressor Lockout - Event
Type
30326 40326 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Clogged Air Filter - Event Control 30327 40327 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Clogged Air Filter - Event Type 30328 40328 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Loss of Air Blower - Event
Control
30329 40329 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Loss of Air Blower - Event Type 30330 40330 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor High Head Pressure -
Event Control 1
30331 40331 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor High Head Pressure -
Event Control 2
30332 40332 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor High Head Pressure -
Event Type 1
30333 40333 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor High Head Pressure -
Event Type 2
30334 40334 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Low Suction Pressure -
Event Control 1
30335 40335 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Low Suction Pressure -
Event Control 2
30336 40336 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Low Suction Pressure -
Event Type 1
30337 40337 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Low Suction Pressure -
Event Type 2
30338 40338 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Pump Down Issue -
Event Control 1
30339 40339 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Pump Down Issue -
Event Control 2
30340 40340 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Pump Down Issue -
Event Type 1
30341 40341 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Pump Down Issue -
Event Type 2
30342 40342 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Short Cycle - Event
Control 1
30343 40343 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Short Cycle - Event
Control 2
30344 40344 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Short Cycle - Event
Type 1
30345 40345 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra