Technical Specifications
BACnet Communications - Thermal Management Products
271 Liebert
®
IntelliSlot
®
Modbus/BACnet
High Return Humidity - Event
Type
MultiState_Value 235 5138_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Low Return Humidity - Event
Control
MultiState_Value 236 5139_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Low Return Humidity - Event
Type
MultiState_Value 237 5140_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Return Air Over Temp - Event
Control
MultiState_Value 238 5024_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Return Air Over Temp - Event
Type
MultiState_Value 239 5025_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Return Air Under Temp - Event
Control
MultiState_Value 240 5407_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Return Air Under Temp - Event
Type
MultiState_Value 241 5408_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Supply Air Over/Under
Temperature - Event Control
MultiState_Value 242 5587_1_1 RW
1 = disabled
2 = enabled
2, 3, 4, 5,
6, 7, 8, 9
System Event Configuration - Fan
Fan Hours Exceeded - Event
Control
MultiState_Value 252 5409_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Fan Hours Exceeded - Event
Type
MultiState_Value 253 5410_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Fan Issue - Event Control MultiState_Value 254 4730_1_1 RW
1 = disabled
2 = enabled
1
Fan Issue - Event Type MultiState_Value 255 4731_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1
Main Fan Overload - Event
Control
MultiState_Value 256 5411_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Main Fan Overload - Event Type MultiState_Value 257 5412_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
System Event Configuration - Condenser
Condenser Issue - Event
Control
MultiState_Value 268 5413_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Condenser Issue - Event Type MultiState_Value 269 5414_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
System Event Configuration - Condenser
Condenser Issue - Event
Control
MultiState_Value 280 5413_1_2 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Condenser Issue - Event Type MultiState_Value 281 5414_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Table 84 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
, Liebert PDX
™
- Multistate Data
Controller Liebert iCOM
®
v4
Data Label Object Type Instance Object Name Access Notes
Extra
Notes