Technical Specifications
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 270
Compressor Low Suction
Pressure - Event Type
MultiState_Value 205 5319_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Pump Down Issue
- Event Control
MultiState_Value 206 5395_1_2 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Pump Down Issue
- Event Type
MultiState_Value 207 5396_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Short Cycle - Event
Control
MultiState_Value 208 5397_1_2 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Short Cycle - Event
Type
MultiState_Value 209 5398_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Thermal Overload -
Event Control
MultiState_Value 210 5320_1_2 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Thermal Overload -
Event Type
MultiState_Value 211 5321_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Dig Scroll Comp Discharge
Over Temp - Event Ctrl
MultiState_Value 212 5399_1_2 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Dig Scroll Comp Discharge
Over Temp - Event Type
MultiState_Value 213 5400_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
System Event Configuration - Air
Ext Air Sensor A Event Control MultiState_Value 224 5401_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Return Air Sensor Event Control MultiState_Value 225 5402_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Air Sensor A High Humidity -
Event Control
MultiState_Value 226 5403_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Air Sensor A High Humidity -
Event Type
MultiState_Value 227 5404_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Air Sensor A Low Humidity -
Event Control
MultiState_Value 228 5405_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Air Sensor A Low Humidity -
Event Type
MultiState_Value 229 5406_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Air Sensor A Over Temp -
Event Control
MultiState_Value 230 4602_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Air Sensor A Over Temp -
Event Type
MultiState_Value 231 4603_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Air Sensor A Under Temp -
Event Control
MultiState_Value 232 4609_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Air Sensor A Under Temp -
Event Type
MultiState_Value 233 4610_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
High Return Humidity - Event
Control
MultiState_Value 234 5137_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Table 84 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
, Liebert PDX
™
- Multistate Data
Controller Liebert iCOM
®
v4
Data Label Object Type Instance Object Name Access Notes
Extra
Notes