Technical Specifications
BACnet Communications - Thermal Management Products
269 Liebert
®
IntelliSlot
®
Modbus/BACnet
Clogged Air Filter - Event
Control
MultiState_Value 166 5135_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Clogged Air Filter - Event Type MultiState_Value 167 5136_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Loss of Air Blower - Event
Control
MultiState_Value 168 5393_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Loss of Air Blower - Event
Type
MultiState_Value 169 5394_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
System Event Configuration - Compressor 1
Compressor High Head
Pressure - Event Control
MultiState_Value 180 5316_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor High Head
Pressure - Event Type
MultiState_Value 181 5317_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Low Suction
Pressure - Event Control
MultiState_Value 182 5318_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Low Suction
Pressure - Event Type
MultiState_Value 183 5319_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Pump Down Issue
- Event Control
MultiState_Value 184 5395_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Pump Down Issue
- Event Type
MultiState_Value 185 5396_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Short Cycle - Event
Control
MultiState_Value 186 5397_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Short Cycle - Event
Type
MultiState_Value 187 5398_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Thermal Overload -
Event Control
MultiState_Value 188 5320_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Thermal Overload -
Event Type
MultiState_Value 189 5321_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Dig Scroll Comp Discharge
Over Temp - Event Ctrl
MultiState_Value 190 5399_1_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Dig Scroll Comp Discharge
Over Temp - Event Type
MultiState_Value 191 5400_1_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
System Event Configuration - Compressor 2
Compressor High Head
Pressure - Event Control
MultiState_Value 202 5316_1_2 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor High Head
Pressure - Event Type
MultiState_Value 203 5317_1_2 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Low Suction
Pressure - Event Control
MultiState_Value 204 5318_1_2 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Table 84 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
, Liebert PDX
™
- Multistate Data
Controller Liebert iCOM
®
v4
Data Label Object Type Instance Object Name Access Notes
Extra
Notes