Technical Specifications

BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 268
Ext Over Temperature - Event
Control
MultiState_Value 146 5090_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Over Temperature - Event
Type
MultiState_Value 147 5091_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Reheat Lockout - Event
Control
MultiState_Value 148 5084_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Reheat Lockout - Event
Type
MultiState_Value 149 5085_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
High Power Shutdown - Event
Control
MultiState_Value 150 5141_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
High Power Shutdown - Event
Type
MultiState_Value 151 5142_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Humidifier Issue - Event Control MultiState_Value 152 5131_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Humidifier Issue - Event Type MultiState_Value 153 5132_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Master Unit Communication
Lost - Event Control
MultiState_Value 154 5133_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Master Unit Communication
Lost - Event Type
MultiState_Value 155 5134_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Service Required - Event
Control
MultiState_Value 156 4727_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Service Required - Event Type MultiState_Value 157 4728_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Shutdown - Loss Of Power -
Event Control
MultiState_Value 158 4715_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Shutdown - Loss Of Power -
Event Type
MultiState_Value 159 4716_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Smoke Detected - Event Control MultiState_Value 160 4721_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Smoke Detected - Event Type MultiState_Value 161 4722_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Water Under Floor - Event
Control
MultiState_Value 162 4724_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Water Under Floor - Event Type MultiState_Value 163 4725_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Compressor Lockout - Event
Control
MultiState_Value 164 5088_1 RW
1 = disabled
2 = enabled
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Compressor Lockout - Event
Type
MultiState_Value 165 5089_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Table 84 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
, Liebert PDX
- Multistate Data
Controller Liebert iCOM
®
v4
Data Label Object Type Instance Object Name Access Notes
Extra
Notes