Technical Specifications
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 264
Liebert Condensers - Condenser 2 Fan 2
Condenser Fan Speed Analog_Value 2023 5276_1_2_2 RD Units: % 4, 9
Condenser Fan Power Analog_Value 2031 5538_1_2_2 RD Units: kW 4, 9
Liebert Condensers - Condenser 2 Fan 3
Condenser Fan Speed Analog_Value 2024 5276_1_2_3 RD Units: % 4, 9
Condenser Fan Power Analog_Value 2032 5538_1_2_3 RD Units: kW 4, 9
Liebert Condensers - Condenser 2 Fan
Condenser Fan Speed Analog_Value 2025 5276_1_2_4 RD Units: % 4, 9
Condenser Fan Power Analog_Value 2033 5538_1_2_4 RD Units: kW 4, 9
PDX
Actual Cold Aisle Humidity Analog_Value 2044 6085_1 RD Units: % RH —
Actual Cold Aisle Temperature Analog_Value 2045 6086_1 RD Units: deg C —
Actual Cold Aisle Temperature Analog_Value 12045 6086_1_deg_F RD Units: deg F —
Cold Aisle Cascade Fan
Speed Max Set Point
Analog_Value 2046 6087_1 RD Units: % —
Cold Aisle Fan Speed Min Set
Point
Analog_Value 2047 6088_1 RD Units: % —
Cold Aisle Fan Speed Max Set
Point
Analog_Value 2048 6089_1 RD Units: % —
Humidification Fan Speed Min
Set Point
Analog_Value 2049 6096_1 RD Units: % —
Heating Fan Speed Min Set
Point
Analog_Value 2050 6097_1 RD Units: % —
Dehumidification Fan Speed
Min Set Point
Analog_Value 2051 6098_1 RD Units: % —
Back Draft Control Fan Speed Analog_Value 2052 6099_1 RD Units: % —
Table 83 Extra Notes to Table 82
Number Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.29.03R
4
This point is supported on:
iCOM controller version 2.01.29.06R
5
This point is supported on:
iCOM controller version 2.01.40R
6
This point is supported on:
iCOM controller version 2.02.21R
7
This point is supported on:
iCOM controller version 2.03.27.06R
8
This point is supported on:
iCOM controller version 2.03.32R
9
This point is supported on:
iCOM controller version 2.03.33R
Table 82 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
, Liebert PDX
™
- Analog Data
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance Object Name Access Notes
Extra