Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
21 Liebert
®
IntelliSlot
®
Modbus/BACnet
Ext Loss of Flow - Event Type 30306 40306 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Over Temperature - Event
Control
30307 40307 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Over Temperature - Event Type 30308 40308 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Reheat Lockout - Event Control 30309 40309 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Reheat Lockout - Event Type 30310 40310 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
High Power Shutdown - Event
Control
30311 40311 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
High Power Shutdown - Event Type 30312 40312 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Humidifier Issue - Event Control 30313 40313 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Humidifier Issue - Event Type 30314 40314 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Master Unit Communication Lost -
Event Control
30315 40315 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Master Unit Communication Lost -
Event Type
30316 40316 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Service Required - Event Control 30317 40317 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Service Required - Event Type 30318 40318 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Shutdown - Loss Of Power - Event
Control
30319 40319 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Shutdown - Loss Of Power - Event
Type
30320 40320 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Smoke Detected - Event Control 30321 40321 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Smoke Detected - Event Type 30322 40322 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Water Under Floor - Event Control 30323 40323 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Water Under Floor - Event Type 30324 40324 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Compressor Lockout - Event
Control
30325 40325 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes