Technical Specifications
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 262
System Input RMS B-C Analog_Value 1952 4099_6 RD Units: VAC 5
System Input RMS C-A Analog_Value 1953 4101_6 RD Units: VAC 5
Fluid 1
Fluid Input Temperature Analog_Value 871 5897_1 RD Units: deg C 5
Fluid Input Temperature Analog_Value 10871 5897_1_deg_F RD Units: deg F 5
Fluid Output Temperature Analog_Value 872 5898_1 RD Units: deg C 5
Fluid Output Temperature Analog_Value 10872 5898_1_deg_F RD Units: deg F 5
Fluid 2
Fluid Input Temperature Analog_Value 1871 5897_2 RD Units: deg C 5
Fluid Input Temperature Analog_Value 11871 5897_2_deg_F RD Units: deg F 5
Fluid Output Temperature Analog_Value 1872 5898_2 RD Units: deg C 5
Fluid Output Temperature Analog_Value 11872 5898_2_deg_F RD Units: deg F 5
Circuit
Fluid Flow Rate Analog_Value 881 5899_1 RD Units: l/min 5
Circuit 2
Fluid Flow Rate Analog_Value 891 5899_2 RD Units: l/min 5
System Operations - Cooling Load 1
Circuit Cooling Load Analog_Value 901 5905_1_1 RD Units: kW 5
System Operations - Cooling Load 2
Circuit Cooling Load Analog_Value 911 5905_1_2 RD Units: kW 5
Auxiliary Air
Raw Auxiliary Air Temperature Analog_Value 1960 5964_1 RW Units: deg C 5
Raw Auxiliary Air Temperature Analog_Value 11960 5964_1_deg_F RW Units: deg F 5
Actual Auxiliary Air
Temperature
Analog_Value 1961 5965_1 RD Units: deg C 5
Actual Auxiliary Air
Temperature
Analog_Value 11961 5965_1_deg_F RD Units: deg F 5
Liebert Condensers (Previously called Global Condensers)
Expected Condenser Unit
Count
Analog_Value 1981 6101_1 RD 4, 9
Liebert Condensers - Low Noise Mode
Condenser Low Noise Mode
Max Fan Speed
Analog_Value 529 5548_1_1 RW Units: %
3, 4, 5, 6,
7, 8, 9
Condenser Normal Mode Max
Fan Speed
Analog_Value 530 5549_1_1 RW Units: %
3, 4, 5, 6,
7, 8, 9
Condenser Low Noise Mode
Start Time
Analog_Value 531 5552_1_1 RW
Units: Seconds
since Midnight
3, 4, 5, 6,
7, 8, 9
Condenser Low Noise Mode
Stop Time
Analog_Value 532 5553_1_1 RW
Units: Seconds
since Midnight
3, 4, 5, 6,
7, 8, 9
Condenser Low Noise Mode -
Interval Days
Analog_Value 533 5550_1_1 RW
1 = Monday
2 = Tuesday
4 = Wednesday
8 = Thursday
16 = Friday
32 = Saturday
64 = Sunday
3, 4, 5, 6,
7, 8, 9
Table 82 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
, Liebert PDX
™
- Analog Data
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance Object Name Access Notes
Extra
Notes