Technical Specifications
BACnet Communications - Thermal Management Products
259 Liebert
®
IntelliSlot
®
Modbus/BACnet
Remote Sensors - Remote Sensor 3
Remote Sensor Temperature Analog_Value 353 5059_1_3 RD Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensor Temperature Analog_Value 10353 5059_1_3_deg_F RD Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensors - Remote Sensor 4
Remote Sensor Temperature Analog_Value 365 5059_1_4 RD Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensor Temperature Analog_Value 10365 5059_1_4_deg_F RD Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensors - Remote Sensor 5
Remote Sensor Temperature Analog_Value 377 5059_1_5 RD Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensor Temperature Analog_Value 10377 5059_1_5_deg_F RD Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensors - Remote Sensor 6
Remote Sensor Temperature Analog_Value 389 5059_1_6 RD Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensor Temperature Analog_Value 10389 5059_1_6_deg_F RD Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensors - Remote Sensor 7
Remote Sensor Temperature Analog_Value 401 5059_1_7 RD Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensor Temperature Analog_Value 10401 5059_1_7_deg_F RD Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensors - Remote Sensor 8
Remote Sensor Temperature Analog_Value 413 5059_1_8 RD Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensor Temperature Analog_Value 10413 5059_1_8_deg_F RD Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensors - Remote Sensor 9
Remote Sensor Temperature Analog_Value 425 5059_1_9 RD Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensor Temperature Analog_Value 10425 5059_1_9_deg_F RD Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensors - Remote Sensor 10
Remote Sensor Temperature Analog_Value 437 5059_1_10 RD Units: deg C
2, 3, 4, 5,
6, 7, 8, 9
Remote Sensor Temperature Analog_Value 10437 5059_1_10_deg_F RD Units: deg F
2, 3, 4, 5,
6, 7, 8, 9
Static Pressure
Static Pressure Set Point Analog_Value 461 5626_1 RW Units: Pa 3, 4, 5, 9
Unit Static Pressure Analog_Value 462 5627_1 RD Units: Pa 3, 4, 5, 9
System Static Pressure Analog_Value 463 5628_1 RD Units: Pa 3, 4, 5, 9
EconoPhase - Pump 1
Pump Hours Analog_Value 523 5298_1_1 RW Units: hr 7, 8, 9
EconoPhase - Pump 2
Table 82 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
, Liebert PDX
™
- Analog Data
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance Object Name Access Notes
Extra
Notes