Technical Specifications
BACnet Communications - Thermal Management Products
255 Liebert
®
IntelliSlot
®
Modbus/BACnet
Compressors - Compressor 1
Compressor Hours Analog_Value 97 5267_1_1 RW Units: hr
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Hours Threshold Analog_Value 98 5268_1_1 RW Units: hr
1, 2, 3, 4,
5, 6, 7, 8, 9
Dig Scroll Comp Discharge
Temp
Analog_Value 99 5353_1_1 RD Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Dig Scroll Comp Discharge
Temp
Analog_Value 10099 5353_1_1_deg_F RD Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Digital Scroll Compressor
Loading
Analog_Value 100 5619_1_1 RD Units: %
3, 4, 5, 6,
7, 8, 9
Compressors - Compressor 2
Compressor Hours Analog_Value 110 5267_1_2 RW Units: hr
1, 2, 3, 4,
5, 6, 7, 8, 9
Compressor Hours Threshold Analog_Value 111 5268_1_2 RW Units: hr
1, 2, 3, 4,
5, 6, 7, 8, 9
Dig Scroll Comp Discharge
Temp
Analog_Value 112 5353_1_2 RD Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Dig Scroll Comp Discharge
Temp
Analog_Value 10112 5353_1_2_deg_F RD Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Digital Scroll Compressor
Loading
Analog_Value 113 5619_1_2 RD Units: %
3, 4, 5, 6,
7, 8, 9
Free Cooling / Chilled Water
Free Cooling Internal
Temperature Delta
Analog_Value 123 5356_1 RW Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Free Cooling Internal
Temperature Delta
Analog_Value 10123 5356_1_deg_F RW Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Free Cooling Fluid
Temperature
Analog_Value 124 5358_1 RD Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Free Cooling Fluid
Temperature
Analog_Value 10124 5358_1_deg_F RD Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Minimum Chilled Water Temp
Set Point
Analog_Value 125 5360_1 RW Units: deg C
1, 2, 3, 4,
5, 6, 7, 8, 9
Minimum Chilled Water Temp
Set Point
Analog_Value 10125 5360_1_deg_F RW Units: deg F
1, 2, 3, 4,
5, 6, 7, 8, 9
Free Cooling Valve Hours Analog_Value 126 5304_1 RW Units: hr
1, 2, 3, 4,
5, 6, 7, 8, 9
Free Cooling Valve Hours
Threshold
Analog_Value 127 5305_1 RW Units: hr
1, 2, 3, 4,
5, 6, 7, 8, 9
Chilled Water Valve Hours Analog_Value 128 5614_1 RW Units: hr
2, 3, 4, 5,
6, 7, 8, 9
Reheat
Hot Water / Hot Gas Valve
Hours
Analog_Value 138 5363_1 RW Units: hr
1, 2, 3, 4,
5, 6, 7, 8, 9
Hot Water / Hot Gas Valve
Hours Threshold
Analog_Value 139 5364_1 RW Units: hr
1, 2, 3, 4,
5, 6, 7, 8, 9
Table 82 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
, Liebert PDX
™
- Analog Data
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance Object Name Access Notes
Extra
Notes