Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 20
Maintenance Tracking State 30286 — 1 —
0 = off
1 = on
1, 2, 3, 4, 5, 6,
7, 8, 9
Customer Input 1 - Event Control 30287 40287 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Customer Input 1 - Event Type 30288 40288 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Customer Input 2 - Event Control 30289 40289 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Customer Input 2 - Event Type 30290 40290 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Customer Input 3 - Event Control 30291 40291 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Customer Input 3 - Event Type 30292 40292 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Customer Input 4 - Event Control 30293 40293 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Customer Input 4 - Event Type 30294 40294 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Free Cooling Lockout - Event
Control
30295 40295 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Free Cooling Lockout - Event
Type
30296 40296 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Condenser Pump High Water -
Event Control
30297 40297 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Condenser Pump High Water -
Event Type
30298 40298 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Standby Glycol Pump On -
Event Control
30299 40299 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Standby Glycol Pump On -
Event Type
30300 40300 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Standby Unit On - Event Control 30301 40301 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Standby Unit On - Event Type 30302 40302 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Humidifier Lockout - Event
Control
30303 40303 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Humidifier Lockout - Event Type 30304 40304 1 —
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Loss of Flow - Event Control 30305 40305 1 —
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6,
7, 8, 9
Table 8 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes