Technical Specifications

BACnet Communications - Thermal Management Products
251 Liebert
®
IntelliSlot
®
Modbus/BACnet
Condenser Supply Refrigerant
Under Temp
Binary_Value 1113 5543_1_2 RD Active on Alarm 4, 9
Condenser Supply Refrigerant
Over Temp
Binary_Value 1115 5542_1_2 RD Active on Alarm 4, 9
Condenser Max Fan Speed
Override
Binary_Value 1117 5545_1_2 RD Active on Alarm 4, 9
Liebert Condensers - Condenser 1 Fan 1
Condenser Fan Issue Binary_Value 1128 5277_1_1_1 RD Active on Alarm 4, 9
Liebert Condensers - Condenser 1 Fan 2
Condenser Fan Issue Binary_Value 1129 5277_1_1_2 RD Active on Alarm 4, 9
Liebert Condensers - Condenser 1 Fan 3
Condenser Fan Issue Binary_Value 1130 5277_1_1_3 RD Active on Alarm 4, 9
Liebert Condensers - Condenser 1 Fan 4
Condenser Fan Issue Binary_Value 1131 5277_1_1_4 RD Active on Alarm 4, 9
Liebert Condensers - Condenser 2 Fan 1
Condenser Fan Issue Binary_Value 1132 5277_1_2_1 RD Active on Alarm 4, 9
Liebert Condensers - Condenser 2 Fan 2
Condenser Fan Issue Binary_Value 1133 5277_1_2_2 RD Active on Alarm 4, 9
Liebert Condensers - Condenser 2 Fan 3
Condenser Fan Issue Binary_Value 1134 5277_1_2_3 RD Active on Alarm 4, 9
Liebert Condensers - Condenser 2 Fan 4
Condenser Fan Issue Binary_Value 1135 5277_1_2_4 RD Active on Alarm 4, 9
PDX
Compressor 1B Thermal Overload Binary_Value 1146 6092_1 RD Active on Alarm
Compressor 2B Thermal Overload Binary_Value 1147 6093_1 RD Active on Alarm
Compressor 1B Hours Exceeded Binary_Value 1148 6094_1 RD Active on Alarm
Compressor 2B Hours Exceeded Binary_Value 1149 6095_1 RD Active on Alarm
Table 81 Extra Notes to Table 80
Number Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3
This point is supported on:
iCOM controller version 2.01.29.03R
4
This point is supported on:
iCOM controller version 2.01.29.06R
5
This point is supported on:
iCOM controller version 2.01.40R
6
This point is supported on:
iCOM controller version 2.02.21R
7
This point is supported on:
iCOM controller version 2.03.27.06R
8
This point is supported on:
iCOM controller version 2.03.32R
9
This point is supported on:
iCOM controller version 2.03.33R
Table 80 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
, Liebert PDX
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Description
Object Type Instance
Object
Name Access Notes
Extra
Notes