Technical Specifications

BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 250
Liebert Condensers (Previously called Global Condensers)
Condenser Unit Unspecified
General Event
Binary_Value 643 5637_1 RD Active on Alarm
3, 4, 5, 6,
7, 8, 9
Liebert Condensers - Condenser 1
Condenser Outside Air Temp Out
of Operating Range
Binary_Value 1082 5536_1_1 RD Active on Alarm 4, 9
Condenser Control Board Issue Binary_Value 1084 5537_1_1 RD Active on Alarm 4, 9
Condenser Outside Air Temp
Sensor Issue
Binary_Value 1086 5535_1_1 RD Active on Alarm 4, 9
Condenser Communication Lost Binary_Value 1088 5531_1_1 RD Active on Alarm 4, 9
Condenser Remote Shutdown Binary_Value 1090 6100_1_1 RD Active on Alarm 4, 9
Condenser TVSS Issue Binary_Value 218 5073_1_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Condenser TVSS Issue Binary_Value 1092 5073_1_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Liebert Condensers - Condenser 2
Condenser Outside Air Temp Out
of Operating Range
Binary_Value 1083 5536_1_2 RD Active on Alarm 4, 9
Condenser Control Board Issue Binary_Value 1085 5537_1_2 RD Active on Alarm 4, 9
Condenser Outside Air Temp
Sensor Issue
Binary_Value 1087 5535_1_2 RD Active on Alarm 4, 9
Condenser Communication Lost Binary_Value 1089 5531_1_2 RD Active on Alarm 4, 9
Liebert Condensers - Circuit 1
Condenser Circuit Unspecified
General Event
Binary_Value 644 5638_1_1 RD Active on Alarm
3, 4, 5, 6,
7, 8, 9
Condenser Refrigerant Pressure
Sensor Issue
Binary_Value 1104 5541_1_1 RD Active on Alarm 4, 9
Condenser Refrigerant Pressure
Under Threshold
Binary_Value 1106 5540_1_1 RD Active on Alarm 4, 9
Condenser Refrigerant Pressure
Over Threshold
Binary_Value 1108 5539_1_1 RD Active on Alarm 4, 9
Condenser Supply Refrigerant
Temp Sensor Issue
Binary_Value 1110 5544_1_1 RD Active on Alarm 4, 9
Condenser Supply Refrigerant
Under Temp
Binary_Value 1112 5543_1_1 RD Active on Alarm 4, 9
Condenser Supply Refrigerant
Over Temp
Binary_Value 1114 5542_1_1 RD Active on Alarm 4, 9
Condenser Max Fan Speed
Override
Binary_Value 1116 5545_1_1 RD Active on Alarm 4, 9
Liebert Condensers - Circuit
Condenser Circuit Unspecified
General Event
Binary_Value 896 5638_1_2 RD Active on Alarm
Condenser Refrigerant Pressure
Sensor Issue
Binary_Value 1105 5541_1_2 RD Active on Alarm 4, 9
Condenser Refrigerant Pressure
Under Threshold
Binary_Value 1107 5540_1_2 RD Active on Alarm 4, 9
Condenser Refrigerant Pressure
Over Threshold
Binary_Value 1109 5539_1_2 RD Active on Alarm 4, 9
Condenser Supply Refrigerant
Temp Sensor Issue
Binary_Value 1111 5544_1_2 RD Active on Alarm 4, 9
Table 80 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
, Liebert PDX
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Description
Object Type Instance
Object
Name Access Notes
Extra
Notes