Technical Specifications

BACnet Communications - Thermal Management Products
249 Liebert
®
IntelliSlot
®
Modbus/BACnet
Static Pressure
Static Pressure Sensor Issue Binary_Value 563 5629_1 RD Active on Alarm
3, 4, 5, 7,
8, 9
High Static Pressure Binary_Value 564 5630_1 RD Active on Alarm
3, 4, 5, 7,
8, 9
Low Static Pressure Binary_Value 565 5631_1 RD Active on Alarm
3, 4, 5, 7,
8, 9
Static Pressure Sensor Out of
Range
Binary_Value 566 5910_1 RD Active on Alarm 4, 5, 7, 8, 9
EconoPhase
Pump Unspecified General Event Binary_Value 623 5636_1 RD Active on Alarm 6, 7, 8, 9
Power Measurement 1
Input Undervoltage Binary_Value 1001 5568_1 RD Active on Alarm 5
Modbus Power Meter
Communication Lost
Binary_Value 1040 5967_1 RD Active on Alarm 5
Power Measurement 2
Input Undervoltage Binary_Value 1002 5568_2 RD Active on Alarm 5
Modbus Power Meter
Communication Lost
Binary_Value 1041 5967_2 RD Active on Alarm 5
Power Measurement 3
Input Undervoltage Binary_Value 1003 5568_3 RD Active on Alarm 5
Modbus Power Meter
Communication Lost
Binary_Value 1042 5967_3 RD Active on Alarm 5
Power Measurement 4
Input Undervoltage Binary_Value 1004 5568_4 RD Active on Alarm 5
Modbus Power Meter
Communication Lost
Binary_Value 1043 5967_4 RD Active on Alarm 5
Power Measurement 5
Input Undervoltage Binary_Value 1005 5568_5 RD Active on Alarm 5
Modbus Power Meter
Communication Lost
Binary_Value 1044 5967_5 RD Active on Alarm 5
Power Measurement 6
Input Undervoltage Binary_Value 1006 5568_6 RD Active on Alarm 5
Modbus Power Meter
Communication Lost
Binary_Value 1045 5967_6 RD Active on Alarm 5
Fluid 1
Fluid Temperature Sensor Issue Binary_Value 1021 5911_1 RD Active on Alarm 5
Fluid Flow Sensor Issue Binary_Value 1022 5912_1 RD Active on Alarm 5
Fluid 2
Fluid Temperature Sensor Issue Binary_Value 1031 5911_2 RD Active on Alarm 5
Fluid Flow Sensor Issue Binary_Value 1032 5912_2 RD Active on Alarm 5
Auxiliary Air
Aux Air Temp Device
Communication Lost
Binary_Value 1050 5966_1 RD Active on Alarm 5
Auxiliary Air
Aux Air Temp Device
Communication Lost
Binary_Value 1050 5966_1 RD Active on Alarm 5
Table 80 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
, Liebert PDX
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Description
Object Type Instance
Object
Name Access Notes
Extra
Notes