Technical Specifications

BACnet Communications - Thermal Management Products
245 Liebert
®
IntelliSlot
®
Modbus/BACnet
Fan
Fan Hours Exceeded Binary_Value 205 5054_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Main Fan Overload Binary_Value 206 5376_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Fan Issue Binary_Value 207 4729_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Condensers
Condenser VFD Issue Binary_Value 219 5072_1 RD Active on Alarm
1, 2, 3, 5,
6, 7, 8
Ext Condenser Pump High Water Binary_Value 220 5106_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
External Condenser TVSS Issue Binary_Value 1060 6105_1 RD Active on Alarm 4, 9
External Condenser VFD Issue Binary_Value 1061 6106_1 RD Active on Alarm 4, 9
Condensers - Condenser 1
Condenser Issue Binary_Value 231 5377_1_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Condensers - Condenser 2
Condenser Issue Binary_Value 242 5377_1_2 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
System Events
Customer Input 1 Binary_Value 253 4270_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Customer Input 2 Binary_Value 254 4271_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Customer Input 3 Binary_Value 255 4272_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Customer Input 4 Binary_Value 256 4273_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Loss of Air Blower Binary_Value 257 5415_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Loss of Flow Binary_Value 258 5105_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Standby Glycol Pump On Binary_Value 259 5107_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
BMS Communications Timeout Binary_Value 260 5115_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Ext Standby Unit On Binary_Value 261 5416_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Clogged Air Filter Binary_Value 262 5118_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Loss of Air Flow Binary_Value 263 5053_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Service Required Binary_Value 264 4726_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Master Unit Communication Lost Binary_Value 265 5120_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
RAM Battery Issue Binary_Value 266 5119_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Shutdown - Loss Of Power Binary_Value 267 4714_1 RD Active on Alarm
1, 2, 3, 4,
5, 6, 7, 8, 9
Table 80 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
, Liebert PDX
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Description
Object Type Instance
Object
Name Access Notes
Extra
Notes