Technical Specifications

BACnet Communications - BACnet Protocol Implementation Conformance Statement
239 Liebert
®
IntelliSlot
®
Modbus/BACnet
4.1.4 Object Properties
The following object properties are supported.
Device Object
The Device object represents the agent (the card) rather than the managed device.
NOTE
All properties are read-only unless otherwise noted
Device Object Property
Comments
Object_Identifier
The card must be configured with a unique Device Instance Number to avoid
interference with other cards on the same BACnet network.
Object_Name
Writable. If the Device Object Name is changed from the default, the configured name
must be unique to avoid interference with other cards on the same BACnet network.
Object_Type
System_Status
Vendor_Name
Vendor_Identifier
Model_Name
Firmware_Revision
Application_Software_Version
Location
Description
Protocol_Version
Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported
Object_List
Max_APDU_Length_Accepted
Segmentation_Supported
Local_Time
Local_Date
UTC_Offset
Daylight_Savings_Status
APDU_Timeout Writable. Range: 1-65,535 ms. Default 3000 ms.
Number_Of_APDU_Retries Writable. Range: 0-8. Default 3.
Device_Address_Binding
Database_Revision
Active_COV_Subscriptions