Technical Specifications
BACnet Communications - BACnet Protocol Implementation Conformance Statement
239 Liebert
®
IntelliSlot
®
Modbus/BACnet
4.1.4 Object Properties
The following object properties are supported.
Device Object
The Device object represents the agent (the card) rather than the managed device.
NOTE
All properties are read-only unless otherwise noted
Device Object Property
Comments
Object_Identifier
The card must be configured with a unique Device Instance Number to avoid
interference with other cards on the same BACnet network.
Object_Name
Writable. If the Device Object Name is changed from the default, the configured name
must be unique to avoid interference with other cards on the same BACnet network.
Object_Type —
System_Status —
Vendor_Name —
Vendor_Identifier —
Model_Name —
Firmware_Revision —
Application_Software_Version —
Location —
Description —
Protocol_Version —
Protocol_Revision —
Protocol_Services_Supported —
Protocol_Object_Types_Supported —
Object_List —
Max_APDU_Length_Accepted —
Segmentation_Supported —
Local_Time —
Local_Date —
UTC_Offset —
Daylight_Savings_Status —
APDU_Timeout Writable. Range: 1-65,535 ms. Default 3000 ms.
Number_Of_APDU_Retries Writable. Range: 0-8. Default 3.
Device_Address_Binding —
Database_Revision —
Active_COV_Subscriptions —