Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 18
Return Humidity 30130 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Humidity 30132 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor B Humidity 30133 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor C Humidity 30134 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Fan Hours 30141 40141 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Hours 1 30142 40142 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Hours 2 30143 40143 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Humidifier Hours 30144 40144 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Dehumidifier Hours 30145 40145 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Free Cooling Valve Hours 30146 40146 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Electric Reheater Hours 1 30147 40147 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Electric Reheater Hours 2 30148 40148 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Electric Reheater Hours 3 30149 40149 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Hot Water / Hot Gas Valve Hours 30150 40150 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Today's High Air Temperature 30151 1 10 deg C
1, 2, 3, 4, 5, 6,
7, 8, 9
Today's High Air Temperature 30752 1 10 deg F
1, 2, 3, 4, 5, 6,
7, 8, 9
Today's Low Air Temperature 30153 1 10 deg C
1, 2, 3, 4, 5, 6,
7, 8, 9
Today's Low Air Temperature 30753 1 10 deg F
1, 2, 3, 4, 5, 6,
7, 8, 9
Today's High Humidity 30155 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Today's Low Humidity 30157 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Server Class 30257 1
1 = UPS
2 = AIR
3 = PMP
4 = PDU
1, 2, 3, 4, 5, 6,
7, 8, 9
Today's High Air Temperature Time 30258 2 Seconds since Midnight
1, 2, 3, 4, 5, 6,
7, 8, 9
Today's Low Air Temperature Time 30260 2 Seconds since Midnight
1, 2, 3, 4, 5, 6,
7, 8, 9
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes