Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 16
Return Air Over Temp Threshold 30739 40739 1 10 deg F
1, 2, 3, 4, 5, 6,
7, 8, 9
Return Air Under Temp Threshold 30051 40051 1 10 deg C
1, 2, 3, 4, 5, 6,
7, 8, 9
Return Air Under Temp Threshold 30740 40740 1 10 deg F
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Over Temp
Threshold
30052 40052 1 10 deg C
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Over Temp
Threshold
30741 40741 1 10 deg F
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Under Temp
Threshold
30053 40053 1 10 deg C
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Under Temp
Threshold
30742 40742 1 10 deg F
1, 2, 3, 4, 5, 6,
7, 8, 9
High Return Humidity Threshold 30054 40054 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Low Return Humidity Threshold 30055 40055 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A High Humidity
Threshold
30056 40056 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Ext Air Sensor A Low Humidity
Threshold
30057 40057 1 10 % RH
1, 2, 3, 4, 5, 6,
7, 8, 9
Fan Hours Threshold 30070 40070 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Hours Threshold 1 30071 40071 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Compressor Hours Threshold 2 30072 40072 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Humidifier Hours Threshold 30073 40073 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Dehumidifier Hours Threshold 30074 40074 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Free Cooling Valve Hours Threshold 30075 40075 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Electric Reheater Hours Threshold 1 30076 40076 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Electric Reheater Hours Threshold 2 30077 40077 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Electric Reheater Hours Threshold 3 30078 40078 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
Hot Water / Hot Gas Valve Hours
Threshold
30079 40079 1 hr
1, 2, 3, 4, 5, 6,
7, 8, 9
System Operating State 30100 1
0 = off
1 = on
2 = standby
1, 2, 3, 4, 5, 6,
7, 8, 9
System Status 30102 1
1 = Normal Operation
2 = StartUp
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
1, 2, 3, 4, 5, 6,
7, 8, 9
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes