Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 14
Condenser Fan Issue 1 10723 — 1 Active on Alarm 4, 9
Condenser Fan Issue 2 10724 — 1 Active on Alarm 4, 9
Condenser Fan Issue 3 10725 — 1 Active on Alarm 4, 9
Condenser Fan Issue 4 10726 — 1 Active on Alarm 4, 9
Condenser Fan Issue 5 10727 — 1 Active on Alarm 4, 9
Condenser Fan Issue 6 10728 — 1 Active on Alarm 4, 9
Condenser Fan Issue 7 10729 — 1 Active on Alarm 4, 9
Condenser Fan Issue 8 10730 — 1 Active on Alarm 4, 9
Table 7 Extra notes key to Table 6
Number
Description
1
This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China - language corrections only)
3
This point is supported on:
iCOM controller version 2.01.29.03R
4
This point is supported on:
iCOM controller version 2.01.29.06R
5
This point is supported on:
iCOM controller version 2.01.40R
6
This point is supported on:
iCOM controller version 2.02.21R
7
This point is supported on:
iCOM controller version 2.03.27.06R
8
This point is supported on:
iCOM controller version 2.03.32R
9
This point is supported on:
iCOM controller version 2.03.33R
Table 6 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes Extra Notes