Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
13 Liebert
®
IntelliSlot
®
Modbus/BACnet
External Condenser TVSS Issue 10655 — 1 Active on Alarm 4, 9
External Condenser VFD Issue 10656 — 1 Active on Alarm 4, 9
Condenser Outside Air Temp Out of Operating
Range 1
10677 — 1 Active on Alarm 4, 9
Condenser Outside Air Temp Out of Operating
Range 2
10678 — 1 Active on Alarm 4, 9
Condenser Control Board Issue 1 10679 — 1 Active on Alarm 4, 9
Condenser Control Board Issue 2 10680 — 1 Active on Alarm 4, 9
Condenser Outside Air Temp Sensor Issue 1 10681 — 1 Active on Alarm 4, 9
Condenser Outside Air Temp Sensor Issue 2 10682 — 1 Active on Alarm 4, 9
Condenser Communication Lost 1 10683 — 1 Active on Alarm 4, 9
Condenser Communication Lost 2 10684 — 1 Active on Alarm 4, 9
Condenser Remote Shutdown 1 10685 — 1 Active on Alarm 4, 9
Condenser Remote Shutdown 2 10686 — 1 Active on Alarm 4, 9
Condenser TVSS Issue 1 10687 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Condenser TVSS Issue 2 10688 — 1 Active on Alarm 4, 9
Condenser Refrigerant Pressure Sensor Issue 1 10699 — 1 Active on Alarm 4, 9
Condenser Refrigerant Pressure Sensor Issue 2 10700 — 1 Active on Alarm 4, 9
Condenser Refrigerant Pressure Under
Threshold 1
10701 — 1 Active on Alarm 4, 9
Condenser Refrigerant Pressure Under
Threshold 2
10702 — 1 Active on Alarm 4, 9
Condenser Refrigerant Pressure Over Threshold
1
10703 — 1 Active on Alarm 4, 9
Condenser Refrigerant Pressure Over Threshold
2
10704 — 1 Active on Alarm 4, 9
Condenser Supply Refrigerant Temp Sensor
Issue 1
10705 — 1 Active on Alarm 4, 9
Condenser Supply Refrigerant Temp Sensor
Issue 2
10706 — 1 Active on Alarm 4, 9
Condenser Supply Refrigerant Under Temp 1 10707 — 1 Active on Alarm 4, 9
Condenser Supply Refrigerant Under Temp 2 10708 — 1 Active on Alarm 4, 9
Condenser Supply Refrigerant Over Temp 1 10709 — 1 Active on Alarm 4, 9
Condenser Supply Refrigerant Over Temp 2 10710 — 1 Active on Alarm 4, 9
Condenser Max Fan Speed Override 1 10711 — 1 Active on Alarm 4, 9
Condenser Max Fan Speed Override 2 10712 — 1 Active on Alarm 4, 9
Table 6 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes Extra Notes