Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 12
EEV Unspecified General Event 10488 1 Active on Alarm 6, 7, 8, 9
Static Pressure Sensor Issue 10489 1 Active on Alarm 3, 4, 5, 7, 8, 9
High Static Pressure 10490 1 Active on Alarm 3, 4, 5, 7, 8, 9
Low Static Pressure 10491 1 Active on Alarm 3, 4, 5, 7, 8, 9
Pump Unspecified General Event 10492 1 Active on Alarm 6, 7, 8, 9
Condenser Unit Unspecified General Event 10493 1 Active on Alarm 3, 4, 5, 6, 7, 8, 9
Condenser Circuit Unspecified General Event 10494 1 Active on Alarm 3, 4, 5, 6, 7, 8, 9
Input Undervoltage 1 10500 1 Active on Alarm 5
Input Undervoltage 2 10501 1 Active on Alarm 5
Input Undervoltage 3 10502 1 Active on Alarm 5
Input Undervoltage 4 10503 1 Active on Alarm 5
Input Undervoltage 5 10504 1 Active on Alarm 5
Input Undervoltage 6 10505 1 Active on Alarm 5
Return Humidity Sensor Issue 10600 1 Active on Alarm 4, 5, 7, 8, 9
Compressor Low Differential Pressure Lockout 1 10601 1 Active on Alarm 7, 8, 9
Compressor Low Differential Pressure Lockout 2 10602 1 Active on Alarm 7, 8, 9
Airflow Sensor Issue 10603 1 Active on Alarm 4, 5, 7, 8, 9
Ext Air Damper Position Issue 10604 1 Active on Alarm 4, 5, 7, 8, 9
Ext Power Source A Failure 10605 1 Active on Alarm 4, 5, 7, 8, 9
Ext Power Source B Failure 10606 1 Active on Alarm 4, 5, 7, 8, 9
Static Pressure Sensor Out of Range 10607 1 Active on Alarm 4, 5, 7, 8, 9
Fluid Temperature Sensor Issue 1 10608 1 Active on Alarm 5
Fluid Temperature Sensor Issue 2 10609 1 Active on Alarm 5
Fluid Flow Sensor Issue 1 10610 1 Active on Alarm 5
Fluid Flow Sensor Issue 2 10611 1 Active on Alarm 5
Mixed Mode Lockout 10620 1 Active on Alarm 7, 8, 9
Aux Air Temp Device Communication Lost 10630 1 Active on Alarm 5
Modbus Power Meter Communication Lost 1 10640 1 Active on Alarm 5
Modbus Power Meter Communication Lost 2 10641 1 Active on Alarm 5
Modbus Power Meter Communication Lost 3 10642 1 Active on Alarm 5
Modbus Power Meter Communication Lost 4 10643 1 Active on Alarm 5
Modbus Power Meter Communication Lost 5 10644 1 Active on Alarm 5
Modbus Power Meter Communication Lost 6 10645 1 Active on Alarm 5
Table 6 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes Extra Notes