Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 12
EEV Unspecified General Event 10488 — 1 Active on Alarm 6, 7, 8, 9
Static Pressure Sensor Issue 10489 — 1 Active on Alarm 3, 4, 5, 7, 8, 9
High Static Pressure 10490 — 1 Active on Alarm 3, 4, 5, 7, 8, 9
Low Static Pressure 10491 — 1 Active on Alarm 3, 4, 5, 7, 8, 9
Pump Unspecified General Event 10492 — 1 Active on Alarm 6, 7, 8, 9
Condenser Unit Unspecified General Event 10493 — 1 Active on Alarm 3, 4, 5, 6, 7, 8, 9
Condenser Circuit Unspecified General Event 10494 — 1 Active on Alarm 3, 4, 5, 6, 7, 8, 9
Input Undervoltage 1 10500 — 1 Active on Alarm 5
Input Undervoltage 2 10501 — 1 Active on Alarm 5
Input Undervoltage 3 10502 — 1 Active on Alarm 5
Input Undervoltage 4 10503 — 1 Active on Alarm 5
Input Undervoltage 5 10504 — 1 Active on Alarm 5
Input Undervoltage 6 10505 — 1 Active on Alarm 5
Return Humidity Sensor Issue 10600 — 1 Active on Alarm 4, 5, 7, 8, 9
Compressor Low Differential Pressure Lockout 1 10601 — 1 Active on Alarm 7, 8, 9
Compressor Low Differential Pressure Lockout 2 10602 — 1 Active on Alarm 7, 8, 9
Airflow Sensor Issue 10603 — 1 Active on Alarm 4, 5, 7, 8, 9
Ext Air Damper Position Issue 10604 — 1 Active on Alarm 4, 5, 7, 8, 9
Ext Power Source A Failure 10605 — 1 Active on Alarm 4, 5, 7, 8, 9
Ext Power Source B Failure 10606 — 1 Active on Alarm 4, 5, 7, 8, 9
Static Pressure Sensor Out of Range 10607 — 1 Active on Alarm 4, 5, 7, 8, 9
Fluid Temperature Sensor Issue 1 10608 — 1 Active on Alarm 5
Fluid Temperature Sensor Issue 2 10609 — 1 Active on Alarm 5
Fluid Flow Sensor Issue 1 10610 — 1 Active on Alarm 5
Fluid Flow Sensor Issue 2 10611 — 1 Active on Alarm 5
Mixed Mode Lockout 10620 — 1 Active on Alarm 7, 8, 9
Aux Air Temp Device Communication Lost 10630 — 1 Active on Alarm 5
Modbus Power Meter Communication Lost 1 10640 — 1 Active on Alarm 5
Modbus Power Meter Communication Lost 2 10641 — 1 Active on Alarm 5
Modbus Power Meter Communication Lost 3 10642 — 1 Active on Alarm 5
Modbus Power Meter Communication Lost 4 10643 — 1 Active on Alarm 5
Modbus Power Meter Communication Lost 5 10644 — 1 Active on Alarm 5
Modbus Power Meter Communication Lost 6 10645 — 1 Active on Alarm 5
Table 6 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes Extra Notes