Technical Specifications

Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 10
Digital Output Board Not Detected 1 10224 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Digital Output Board Not Detected 2 10225 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Digital Output Board Not Detected 3 10226 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
RAM Battery Issue 10227 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Water Leakage Detector Sensor Issue 10228 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
External Fire Detected 10229 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Chilled Water Control Valve Failure 1 10230 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Chilled Water Control Valve Failure 2 10231 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Unit Off 10232 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Unit On 10233 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Unit Partial Shutdown 10234 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Unit Shutdown 10235 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
High Power Shutdown 10236 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Unit Standby 10237 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Maintenance Due 10238 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Maintenance Completed 10239 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor Low Pressure Transducer Issue 1 10240 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor Low Pressure Transducer Issue 2 10241 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor High Pressure Transducer Issue 1 10242 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor High Pressure Transducer Issue 2 10243 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor Capacity Reduced 10244 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Dew Point Over Temperature 10345 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Dew Point Under Temperature 10346 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Ext Dew Point Over Temperature 10347 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Ext Dew Point Under Temperature 10348 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Compressor Superheat Over Threshold 1 10349 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Compressor Superheat Over Threshold 2 10350 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Unspecified General Event 10351 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Remote Sensor Average Over Temperature 10352 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Remote Sensor Average Under Temperature 10353 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Remote Sensor System Average Over
Temperature
10354 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Remote Sensor System Average Under
Temperature
10355 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Table 6 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes Extra Notes