Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
9Liebert
®
IntelliSlot
®
Modbus/BACnet
Free Cooling Valve Hours Exceeded 10083 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Electric Reheater Hours Exceeded 1 10084 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Electric Reheater Hours Exceeded 2 10085 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Electric Reheater Hours Exceeded 3 10086 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Hot Water / Hot Gas Valve Hours Exceeded 10087 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Humidifier Hours Exceeded 10088 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Dehumidifier Hours Exceeded 10089 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Unit Communication Lost 10091 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Master Unit Communication Lost 10092 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Unit Code Missing 10094 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Service Required 10098 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Humidifier Control Board Not Detected 10099 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Customer Input 1 10104 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Customer Input 2 10105 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Customer Input 3 10106 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Customer Input 4 10107 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Dig Scroll Comp Discharge Temp Sensor Issue 1 10108 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Dig Scroll Comp Discharge Temp Sensor Issue 2 10109 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Supply Air Over Temperature 10209 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Supply Air Under Temperature 10210 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ambient Air Sensor Issue 10211 — 1 Active on Alarm 2, 3, 4, 5, 6, 7, 8, 9
Compressor Short Cycle 1 10212 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor Short Cycle 2 10213 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Free Cooling Lockout 10214 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Reheater Over Temperature 10215 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Humidifier Cylinder Worn 10216 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Humidifier Under Current 10217 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Fan Issue 10218 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Condenser TVSS Issue 10219 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Condenser VFD Issue 10220 — 1 Active on Alarm 1, 2, 3, 5, 6, 7, 8
Condenser Issue 1 10221 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Condenser Issue 2 10222 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
BMS Communications Timeout 10223 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Table 6 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes Extra Notes