Technical Specifications

Modbus RTU and Modbus TCP Protocols - UPS Systems
143 Liebert
®
IntelliSlot
®
Modbus/BACnet
User Operation Invalid 10050 1 Active on Alarm
Power Sub Module Fault 10051 1 Active on Alarm
Battery Discharging 10052 1 Active on Alarm
UPS Output on Bypass 10053 1 Active on Alarm
Output Load on Maint. Bypass 10054 1 Active on Alarm
Battery Capacity Low 10055 1 Active on Alarm
MMS On Battery 10056 1 Active on Alarm
Loss of Redundancy 10057 1 Active on Alarm
Top Outlet Fan Fault 10058 1 Active on Alarm
MMS Over Capacity 10059 1 Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 45 Liebert APM
, Liebert NXC
, Liebert NXR
- Input and Holding
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Input
System Input RMS A-B 30385 1 VAC
System Input RMS B-C 30386 1 VAC
System Input RMS C-A 30387 1 VAC
System Input RMS Current Phase A 30388 1 A AC
System Input RMS Current Phase B 30389 1 A AC
System Input RMS Current Phase C 30390 1 A AC
System Input Frequency 30391 1 10 Hz
System Input RMS A-N 30392 1 VAC
System Input RMS B-N 30393 1 VAC
System Input RMS C-N 30394 1 VAC
System Input Power Factor Phs A 30395 1 100
System Input Power Factor Phs B 30396 1 100
System Input Power Factor Phs C 30397 1 100
Bypass
Bypass Input Voltage RMS A-N 30401 1 VAC
Bypass Input Voltage RMS B-N 30402 1 VAC
Bypass Input Voltage RMS C-N 30403 1 VAC
Bypass Input Frequency 30404 1 10 Hz
Battery
Battery Time Remaining 30408 1 min
Battery Volts for Cabinet 30409 1 VDC
Battery Temperature for Cabinet 30410 1 deg C
Battery Temperature for Cabinet 30411 1 deg F
Inlet Air Temperature 30412 1 deg C
Inlet Air Temperature 30413 1 deg F
DC Bus Current 30414 1 A DC
UPS battery1 status 30415 1
1 = Unknown
2 = Normal
3 = Low
4 = Depleted
Table 44 Liebert APM
™,
Liebert NXC
, Liebert NXR
- Status and Coil (continued)
Data Label
Status Coil
Number
of Bits Scale Notes / Units