Technical Specifications
Modbus RTU and Modbus TCP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 8
Compressor Thermal Overload 2 10043 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor Pump Down Issue 2 10044 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Dig Scroll Comp Over Temp 1 10045 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Dig Scroll Comp Over Temp 2 10046 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Smoke Detected 10047 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Water Under Floor 10048 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Humidifier Issue 10049 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Standby Glycol Pump On 10050 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Standby Unit On 10051 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Condenser Pump High Water 10052 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Return Air Sensor Issue 10053 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Loss of Air Blower 10055 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Humidifier Low Water 10058 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Humidifier Over Current 10059 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Over Temperature 10060 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Shutdown - Loss Of Power 10061 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Supply Chilled Water Over Temp 10065 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Return Air Over Temperature 10067 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Return Air Under Temperature 10068 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
High Return Humidity 10069 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Low Return Humidity 10070 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Air Sensor A Over Temperature 10071 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Air Sensor A Under Temperature 10072 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Air Sensor A High Humidity 10073 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Air Sensor A Low Humidity 10074 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Supply Chilled Water Loss of Flow 10075 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Clogged Air Filter 10076 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Supply Air Sensor Issue 10077 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Free Cooling Temp Sensor Issue 10078 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Ext Air Sensor A Issue 10079 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Fan Hours Exceeded 10080 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor Hours Exceeded 1 10081 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Compressor Hours Exceeded 2 10082 — 1 Active on Alarm 1, 2, 3, 4, 5, 6, 7, 8, 9
Table 6 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Status and Coil (continued)
Controller Liebert iCOM
®
v4
Liebert Products
Units with
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status Coil
Number
of Bits Notes Extra Notes