Technical Specifications
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 130
Table 39 Liebert FDC™, Liebert FPC™, Liebert PPC™, Liebert RDC™ - Status and Coil
Controller Liebert CPM
Liebert Products Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC
Available Points
Data Label
Status Coil
Number
of Bits Scale Notes / Units
Panel 1 – Panelboard Main 1 (if panelboards are installed)
Panel Summary Alarm 10065 — 1 — Active on Alarm
Panel Overvoltage 10066 — 1 — Active on Alarm
Panel Undervoltage 10067 — 1 — Active on Alarm
Panel Phase Overcurrent 10068 — 1 — Active on Alarm
Panel Phase Overcurrent 10069 — 1 — Active on Warning
Panel Neutral Overcurrent 10070 — 1 — Active on Alarm
Panel Ground Overcurrent 10071 — 1 — Active on Alarm
Panel 2 – Panelboard Main 2 (if panelboards are installed)
Panel Summary Alarm 10082 — 1 — Active on Alarm
Panel Overvoltage 10083 — 1 — Active on Alarm
Panel Undervoltage 10084 — 1 — Active on Alarm
Panel Phase Overcurrent 10085 — 1 — Active on Alarm
Panel Phase Overcurrent 10086 — 1 — Active on Warning
Panel Neutral Overcurrent 10087 — 1 — Active on Alarm
Panel Ground Overcurrent 10088 — 1 — Active on Alarm
Panel 4 – Panelboard Main 4 (if panelboards are installed)
Panel Summary Alarm 10116 — 1 — Active on Alarm
Panel Overvoltage 10117 — 1 — Active on Alarm
Panel Undervoltage 10118 — 1 — Active on Alarm
Panel Phase Overcurrent 10119 — 1 — Active on Alarm
Panel Phase Overcurrent 10120 — 1 — Active on Warning
Panel Neutral Overcurrent 10121 — 1 — Active on Alarm
Panel Ground Overcurrent 10122 — 1 — Active on Alarm
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.