Technical Specifications

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
129 Liebert
®
IntelliSlot
®
Modbus/BACnet
Subfeed Current Iy THD 34651 1 10 %
Subfeed Current Iz THD 34652 1 10 %
Subfeed Current Ix Crest Factor 34653 1 10
Subfeed Current Iy Crest Factor 34654 1 10
Subfeed Current Iz Crest Factor 34655 1 10
Subfeed 64
Subfeed Current Ix 35879 1 A AC
Subfeed Current Iy 35880 1 A AC
Subfeed Current Iz 35881 1 A AC
Subfeed Neutral Current 35882 1 A AC
Subfeed Ground Current 35883 1 10 A AC
Subfeed Output Power (kVA) 35884 1 kVA
Subfeed Output Power (kW) 35885 1 kW
Subfeed Output kW-Hrs 35886 45886 2 10 kWH
Subfeed Power Factor 35888 1 100
Subfeed Output Percent Load 35889 1 - %
Subfeed Current Ix THD 35890 1 10 %
Subfeed Current Iy THD 35891 1 10 %
Subfeed Current Iz THD 35892 1 10 %
Subfeed Current Ix Crest Factor 35893 1 10
Subfeed Current Iy Crest Factor 35894 1 10
Subfeed Current Iz Crest Factor 35895 1 10
System
System Status 35899 1
1 = Normal
Operation
2 = Startup
8 = Normal with
Warning
16 = Normal
with Alarm
32 = Abnormal
Operation
System Event Acknowledge/Reset 45900 1
2 = Reset
4 =
Acknowledge
System Date and Time 39998 49998 2
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 38 Liebert EXC
, Liebert FDC
, Liebert FPC
, Liebert PPC
, Liebert RDC
, Liebert RX
, Liebert
STS2/PDU
- Input and Holding (continued)
Controller
Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units