Technical Specifications
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
129 Liebert
®
IntelliSlot
®
Modbus/BACnet
Subfeed Current Iy THD 34651 — 1 10 %
Subfeed Current Iz THD 34652 — 1 10 %
Subfeed Current Ix Crest Factor 34653 — 1 10 —
Subfeed Current Iy Crest Factor 34654 — 1 10 —
Subfeed Current Iz Crest Factor 34655 — 1 10 —
Subfeed 64
Subfeed Current Ix 35879 — 1 — A AC
Subfeed Current Iy 35880 — 1 — A AC
Subfeed Current Iz 35881 — 1 — A AC
Subfeed Neutral Current 35882 — 1 — A AC
Subfeed Ground Current 35883 — 1 10 A AC
Subfeed Output Power (kVA) 35884 — 1 — kVA
Subfeed Output Power (kW) 35885 — 1 — kW
Subfeed Output kW-Hrs 35886 45886 2 10 kWH
Subfeed Power Factor 35888 — 1 100 —
Subfeed Output Percent Load 35889 — 1 - %
Subfeed Current Ix THD 35890 — 1 10 %
Subfeed Current Iy THD 35891 — 1 10 %
Subfeed Current Iz THD 35892 — 1 10 %
Subfeed Current Ix Crest Factor 35893 — 1 10 —
Subfeed Current Iy Crest Factor 35894 — 1 10 —
Subfeed Current Iz Crest Factor 35895 — 1 10 —
System
System Status 35899 — 1 —
1 = Normal
Operation
2 = Startup
8 = Normal with
Warning
16 = Normal
with Alarm
32 = Abnormal
Operation
System Event Acknowledge/Reset — 45900 1 —
2 = Reset
4 =
Acknowledge
System Date and Time 39998 49998 2 — —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 38 Liebert EXC
™
, Liebert FDC
™
, Liebert FPC
™
, Liebert PPC
™
, Liebert RDC
™
, Liebert RX
™
, Liebert
STS2/PDU
™
- Input and Holding (continued)
Controller
Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units