Technical Specifications
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
127 Liebert
®
IntelliSlot
®
Modbus/BACnet
Panel 3 Position 2
Breaker position 32615 — 1 — —
Branch Current Phase 1 32616 — 1 10 A AC
Branch Current Phase 2 32617 — 1 10 A AC
Branch Current Phase 3 32618 — 1 10 A AC
Branch Output Power (kW) 32619 — 1 1000 kW
Output kW-Hrs 32620 — 2 1000 kWH
Branch Output Power Factor 32622 — 1 100 —
Branch Output Percent Load 32623 — 1 — %
Panel 3 Position 84
Breaker position 33599 — 1 — —
Branch Current Phase 1 33600 — 1 10 A AC
Branch Current Phase 2 33601 — 1 10 A AC
Branch Current Phase 3 33602 — 1 10 A AC
Branch Output Power (kW) 33603 — 1 1000 kW
Output kW-Hrs 33604 — 2 1000 kWH
Branch Output Power Factor 33606 — 1 100 —
Branch Output Percent Load 33607 — 1 — %
Panel 4 Position 1
Breaker position 33611 — 1 — —
Branch Current Phase 1 33612 — 1 10 A AC
Branch Current Phase 2 33613 — 1 10 A AC
Branch Current Phase 3 33614 — 1 10 A AC
Branch Output Power (kW) 33615 — 1 1000 kW
Output kW-Hrs 33616 — 2 1000 kWH
Branch Output Power Factor 33618 — 1 100 —
Branch Output Percent Load 33619 — 1 — %
Panel 4 Position 2
Breaker position 33623 — 1 — —
Branch Current Phase 1 33624 — 1 10 A AC
Branch Current Phase 2 33625 — 1 10 A AC
Branch Current Phase 3 33626 — 1 10 A AC
Branch Output Power (kW) 33627 — 1 1000 kW
Output kW-Hrs 33628 — 2 1000 kWH
Branch Output Power Factor 33630 — 1 100 —
Branch Output Percent Load 33631 — 1 - %
Table 38 Liebert EXC
™
, Liebert FDC
™
, Liebert FPC
™
, Liebert PPC
™
, Liebert RDC
™
, Liebert RX
™
, Liebert
STS2/PDU
™
- Input and Holding (continued)
Controller
Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units