Technical Specifications

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
127 Liebert
®
IntelliSlot
®
Modbus/BACnet
Panel 3 Position 2
Breaker position 32615 1
Branch Current Phase 1 32616 1 10 A AC
Branch Current Phase 2 32617 1 10 A AC
Branch Current Phase 3 32618 1 10 A AC
Branch Output Power (kW) 32619 1 1000 kW
Output kW-Hrs 32620 2 1000 kWH
Branch Output Power Factor 32622 1 100
Branch Output Percent Load 32623 1 %
Panel 3 Position 84
Breaker position 33599 1
Branch Current Phase 1 33600 1 10 A AC
Branch Current Phase 2 33601 1 10 A AC
Branch Current Phase 3 33602 1 10 A AC
Branch Output Power (kW) 33603 1 1000 kW
Output kW-Hrs 33604 2 1000 kWH
Branch Output Power Factor 33606 1 100
Branch Output Percent Load 33607 1 %
Panel 4 Position 1
Breaker position 33611 1
Branch Current Phase 1 33612 1 10 A AC
Branch Current Phase 2 33613 1 10 A AC
Branch Current Phase 3 33614 1 10 A AC
Branch Output Power (kW) 33615 1 1000 kW
Output kW-Hrs 33616 2 1000 kWH
Branch Output Power Factor 33618 1 100
Branch Output Percent Load 33619 1 %
Panel 4 Position 2
Breaker position 33623 1
Branch Current Phase 1 33624 1 10 A AC
Branch Current Phase 2 33625 1 10 A AC
Branch Current Phase 3 33626 1 10 A AC
Branch Output Power (kW) 33627 1 1000 kW
Output kW-Hrs 33628 2 1000 kWH
Branch Output Power Factor 33630 1 100
Branch Output Percent Load 33631 1 - %
Table 38 Liebert EXC
, Liebert FDC
, Liebert FPC
, Liebert PPC
, Liebert RDC
, Liebert RX
, Liebert
STS2/PDU
- Input and Holding (continued)
Controller
Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units