Technical Specifications

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet 126
Panel 2 Position 1
Breaker position 31595 1 -
Branch Current Phase 1 31596 1 10 A AC
Branch Current Phase 2 31597 1 10 A AC
Branch Current Phase 3 31598 1 10 A AC
Branch Output Power (kW) 31599 1 1000 kW
Output kW-Hrs 31600 2 1000 kWH
Branch Output Power Factor 31602 1 100
Branch Output Percent Load 31603 1 %
Panel 2 Position 2
Breaker position 31607 1
Branch Current Phase 1 31608 1 10 A AC
Branch Current Phase 2 31609 1 10 A AC
Branch Current Phase 3 31610 1 10 A AC
Branch Output Power (kW) 31611 1 1000 kW
Output kW-Hrs 31612 2 1000 kWH
Branch Output Power Factor 31614 1 100
Branch Output Percent Load 31615 1 %
Panel 2 Position 84
Breaker position 32591 1
Branch Current Phase 1 32592 1 10 A AC
Branch Current Phase 2 32593 1 10 A AC
Branch Current Phase 3 32594 1 10 A AC
Branch Output Power (kW) 32595 1 1000 kW
Output kW-Hrs 32596 2 1000 kWH
Branch Output Power Factor 32598 1 100
Branch Output Percent Load 32599 1 %
Panel 3 Position 1
Breaker position 32603 1
Branch Current Phase 1 32604 1 10 A AC
Branch Current Phase 2 32605 1 10 A AC
Branch Current Phase 3 32606 1 10 A AC
Branch Output Power (kW) 32607 1 1000 kW
Output kW-Hrs 32608 2 1000 kWH
Branch Output Power Factor 32610 1 100
Branch Output Percent Load 32611 1 %
Table 38 Liebert EXC
, Liebert FDC
, Liebert FPC
, Liebert PPC
, Liebert RDC
, Liebert RX
, Liebert
STS2/PDU
- Input and Holding (continued)
Controller
Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units