Technical Specifications
Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
125 Liebert
®
IntelliSlot
®
Modbus/BACnet
Panel Main Voltage Vy THD 30576 — 1 10 % THD
Panel Main Voltage Vz THD 30577 — 1 10 % THD
Panel Main Current Ix THD 30578 — 1 10 % THD
Panel Main Current Iy THD 30579 — 1 10 % THD
Panel Main Current Iz THD 30580 — 1 10 % THD
Panel Main Current Ix Crest Factor 30581 — 1 10 —
Panel Main Current Iy Crest Factor 30582 — 1 10 —
Panel Main Current Iz Crest Factor 30583 — 1 10 —
Panel 1 Position 1
Breaker position 30587 — 1 — —
Branch Current Phase 1 30588 — 1 10 A AC
Branch Current Phase 2 30589 — 1 10 A AC
Branch Current Phase 3 30590 — 1 10 A AC
Branch Output Power (kW) 30591 — 1 1000 kW
Output kW-Hrs 30592 — 2 1000 kWH
Branch Output Power Factor 30594 — 1 100 -
Branch Output Percent Load 30595 — 1 — %
Panel 1 Position 2
Breaker position
30599 — 1 — —
Branch Current Phase 1 30600 — 1 10 A AC
Branch Current Phase 2 30601 — 1 10 A AC
Branch Current Phase 3 30602 — 1 10 A AC
Branch Output Power (kW) 30603 — 1 1000 kW
Output kW-Hrs 30604 — 2 1000 kWH
Branch Output Power Factor 30606 — 1 100 —
Branch Output Percent Load 30607 — 1 — %
Panel 1 Position 84
Breaker position 31583 — 1 — —
Branch Current Phase 1 31584 — 1 10 A AC
Branch Current Phase 2 31585 — 1 10 A AC
Branch Current Phase 3 31586 — 1 10 A AC
Branch Output Power (kW) 31587 — 1 1000 kW
Output kW-Hrs 31588 — 2 1000 kWH
Branch Output Power Factor 31590 — 1 100 —
Branch Output Percent Load 31591 — 1 — %
Table 38 Liebert EXC
™
, Liebert FDC
™
, Liebert FPC
™
, Liebert PPC
™
, Liebert RDC
™
, Liebert RX
™
, Liebert
STS2/PDU
™
- Input and Holding (continued)
Controller
Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units