Technical Specifications

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
125 Liebert
®
IntelliSlot
®
Modbus/BACnet
Panel Main Voltage Vy THD 30576 1 10 % THD
Panel Main Voltage Vz THD 30577 1 10 % THD
Panel Main Current Ix THD 30578 1 10 % THD
Panel Main Current Iy THD 30579 1 10 % THD
Panel Main Current Iz THD 30580 1 10 % THD
Panel Main Current Ix Crest Factor 30581 1 10
Panel Main Current Iy Crest Factor 30582 1 10
Panel Main Current Iz Crest Factor 30583 1 10
Panel 1 Position 1
Breaker position 30587 1
Branch Current Phase 1 30588 1 10 A AC
Branch Current Phase 2 30589 1 10 A AC
Branch Current Phase 3 30590 1 10 A AC
Branch Output Power (kW) 30591 1 1000 kW
Output kW-Hrs 30592 2 1000 kWH
Branch Output Power Factor 30594 1 100 -
Branch Output Percent Load 30595 1 %
Panel 1 Position 2
Breaker position
30599 1
Branch Current Phase 1 30600 1 10 A AC
Branch Current Phase 2 30601 1 10 A AC
Branch Current Phase 3 30602 1 10 A AC
Branch Output Power (kW) 30603 1 1000 kW
Output kW-Hrs 30604 2 1000 kWH
Branch Output Power Factor 30606 1 100
Branch Output Percent Load 30607 1 %
Panel 1 Position 84
Breaker position 31583 1
Branch Current Phase 1 31584 1 10 A AC
Branch Current Phase 2 31585 1 10 A AC
Branch Current Phase 3 31586 1 10 A AC
Branch Output Power (kW) 31587 1 1000 kW
Output kW-Hrs 31588 2 1000 kWH
Branch Output Power Factor 31590 1 100
Branch Output Percent Load 31591 1 %
Table 38 Liebert EXC
, Liebert FDC
, Liebert FPC
, Liebert PPC
, Liebert RDC
, Liebert RX
, Liebert
STS2/PDU
- Input and Holding (continued)
Controller
Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units