Technical Specifications

Modbus RTU and Modbus TCP Protocols - Power Distribution and Power Conditioning Products
123 Liebert
®
IntelliSlot
®
Modbus/BACnet
Table 38 Liebert EXC
, Liebert FDC
, Liebert FPC
, Liebert PPC
, Liebert RDC
, Liebert RX
, Liebert
STS2/PDU
- Input and Holding
Controller
Liebert LDMF
Liebert Products
Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC,
Liebert RDC, Liebert RX, Liebert STS2/PDU
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Panel 1
Columns of Breakers 30463 1
Number of Breakers 30464 1
Panel Main Voltage X-Y 30465 1 VAC
Panel Main Voltage Y-Z 30466 1 VAC
Panel Main Voltage Z-X 30467 1 VAC
Panel Main Voltage X-N 30468 1 VAC
Panel Main Voltage Y-N 30469 1 VAC
Panel Main Voltage Z-N 30470 1 VAC
Panel Main Current Ix 30471 1 A AC
Panel Main Current Iy 30472 1 A AC
Panel Main Current Iz 30473 1 A AC
Panel Main Neutral Current 30474 1 A AC
Panel Main Ground Current 30475 1 10 A AC
Panel Main Output Power (kVA) 30476 1 kVA
Panel Main Output Power (kW) 30477 1 kW
Panel Main Output kW-Hrs 30478 40478 2 10 kWH
Panel Main Output Power Factor 30480 1 100
Panel Main Output Percent Load 30481 1 %
Panel Main Voltage Vx THD 30482 1 10 % THD
Panel Main Voltage Vy THD 30483 1 10 % THD
Panel Main Voltage Vz THD 30484 1 10 % THD
Panel Main Current Ix THD 30485 1 10 % THD
Panel Main Current Iy THD 30486 1 10 % THD
Panel Main Current Iz THD 30487 1 10 % THD
Panel Main Current Ix Crest Factor 30488 1 10
Panel Main Current Iy Crest Factor 30489 1 10
Panel Main Current Iz Crest Factor 30490 1 10
Panel 2
Columns of Breakers 30494 1
Number of Breakers 30495 1
Panel Main Voltage X-Y 30496 1 VAC
Panel Main Voltage Y-Z 30497 1 VAC
Panel Main Voltage Z-X 30498 1 VAC
Panel Main Voltage X-N 30499 1 VAC
Panel Main Voltage Y-N 30500 1 VAC
Panel Main Voltage Z-N 30501 1 VAC
Panel Main Current Ix 30502 1 A AC